MECHANICAL INSTALLATION — FUEL SYSTEM

MECHANICAL INSTALLATION — FUEL SYSTEM

Figure 13. Typical Pipe Schematic for Propane Liquid Distribution

TABLE 16. LIQUID PROPANE SCHEDULE 40 IRON PIPE SIZING

Length of

 

 

 

Pipe Size, in.

 

 

 

Pipe, ft.

1/2

3/4

1

1 1/4

1 1/2

2

3

3 1/2

4

(0.622)

(0.824)

(1.049)

(1.38)

(1.61)

(2.067)

(3.068)

(3.548)

(4.026)

 

30

733

1532

2885

5924

8876

17094

48164

70519

98238

40

627

1311

2469

5070

7597

14630

41222

60355

84079

50

556

1162

2189

4494

6733

12966

36534

53492

74518

 

 

 

 

 

 

 

 

 

 

60

504

1053

1983

4072

6100

11748

33103

48467

67519

70

463

969

1824

3746

5612

10808

30454

44589

62116

 

 

 

 

 

 

 

 

 

 

80

431

901

1697

3484

5221

10055

28331

41482

57787

90

404

845

1593

3269

4899

9434

26583

38921

54220

100

382

798

1504

3088

4627

8912

25110

36764

51216

150

307

641

1208

2480

3716

7156

20164

29523

41128

200

262

549

1034

2122

3180

6125

17258

25268

35200

 

 

 

 

 

 

 

 

 

 

250

233

486

916

1881

2819

5428

15295

22395

31198

300

211

441

830

1705

2554

4919

13859

20291

28267

 

 

 

 

 

 

 

 

 

 

350

194

405

764

1568

2349

4525

12750

18667

26006

400

180

377

711

1459

2186

4209

11861

17366

24193

450

169

354

667

1369

2051

3950

11129

16295

22700

500

160

334

630

1293

1937

3731

10512

15391

21442

600

145

303

571

1172

1755

3380

9525

13946

19428

 

 

 

 

 

 

 

 

 

 

700

133

279

525

1078

1615

3110

8763

12830

17873

800

124

259

488

1003

1502

2893

8152

11936

16628

 

 

 

 

 

 

 

 

 

 

900

116

243

458

941

1409

2715

7649

11199

15601

1000

110

230

433

889

1331

2564

7225

10579

14737

1500

88

184

348

713

1069

2059

5802

8495

11834

 

 

 

 

 

 

 

 

 

 

2000

76

158

297

611

915

1762

4966

7271

10128

Please observe the following when servicing natural gas or LPG supply lines:

Open any valve SLOWLY.

DO NOT remove plugs or caps on connections if shut off valves leak.

Make sure all unloading connections are tight.

DO NOT tamper with relief valves.

NEVER place your face or any other part of your body over safety relief valves.

PAGE 44 — INDUSTRIAL GENERATOR SETS — APPLICATION & INSTALLATION MANUAL — REV. #4 (09/07/07)

Page 44
Image 44
Multiquip MQP50IZ Mechanical Installation — Fuel System, •Open any valve SLOWLY, •DO NOT tamper with relief valves