PRE-START PREPARATION

NOTE

For genset inspection, start-up and

 

operational procedures, refer to the

 

MQ Power Operators manual for the

 

genset in use.

General

Before attempting the initial start of the generator set, be sure it is serviced and ready for operation. Perform the following:

zCheck ventilation and exhaust systems

zCheck all mechanical connections

zCheck the lubrication system for leaks

zCheck control configuration options

Battery Connections

Refer to Battery Safety Section on page 11.

The battery cables are supplied with the generator set. Service batteries, if necessary, as specified in the battery section of this manual. Install battery. Connect battery charger and jacket water heater if equipped.

Make sure the Run/Off/Manual switch is in the OFF position before connecting the battery cables. Failure to do so will result in immediate starting of the genset when connecting the generator set.

Ventilation

Verify all vents and ducts are open and free from any obstructions. Verify dampers, if used, operate properly.

Exhaust System

Check the exhaust system for proper installation. Verify there is at least 12 inches (305 mm) clearance between exhaust pipes and combustible materials, all connections are tight, and the exhaust will not disperse near doors, windows, vents, or other openings.

Mechanical Checks

Check the generator set for loose or damaged components and repair or replace as required.

Digital Control

Configure digital control as specified in digital control manual.

Electrical System

Verify all electrical connections are secure and wiring is complete and inspected. Replace and secure any access panels that may have been removed during installation.

Starting

After the installation is complete, make sure the lubricating system is primed and the system is working properly. Routine inspections are recommended.

Refer to the specified genset Operation manual for important safety precautions and recommended procedures for starting the genset. Only use the start-up procedures outlined in the "Genset Operation Manual" when starting of the genset is required.This is important to verify proper operation. Start the genset as outlined in the operation manual and verify all engine and generator display readings are accurate values.

PAGE 80 — INDUSTRIAL GENERATOR SETS — APPLICATION & INSTALLATION MANUAL — REV. #4 (09/07/07)

Page 80
Image 80
Multiquip MQP20IZ, MQP40IZ, MQP45GM, MQP60IV, MQP50IZ, MQP30GM, MQP30DZ, MQP60GM installation manual PRE-START Preparation