Multiquip MQP50IZ Appendix — Main-Linecircuit Breaker, FOR MQ POWER INDUSTRIAL GENERATORS cont

Models: MQP60GM MQP30DZ MQP30GM MQP50IZ MQP60IV MQP45GM MQP40IZ MQP20IZ

1 94
Download 94 pages 19.21 Kb
Page 84
Image 84
APPENDIX — MAIN-LINE CIRCUIT BREAKER

APPENDIX — MAIN-LINE CIRCUIT BREAKER

TABLE 25. FACTORY RECOMMENDED MAIN LINE CIRCUIT BREAKERS

FOR MQ POWER INDUSTRIAL GENERATORS (cont.)

Generator

ABB or

Generator

Generator

Breaker

Breaker

Interrupting

Cable Size

Max. No.

Type Of

Torque Rating

Cutler Hammer

Output

Output

Frame Size

Trip Rating

Rating RMS

(kcmil)

Cables Per

Connection

Of Lugs

Model

Model No.

(Voltage)

(Amps)

(Amps)

(Amps)

(Sym Amps)

{Note 1}

Phase

{Note 2}

(in./lbs.)

 

 

 

 

 

 

 

 

 

 

 

 

 

KG3350

240V - 1Ø

333

400

350

 

250 ~ 500

1

 

375

 

 

 

 

 

 

 

 

 

 

 

MQP150IV

LG3600

208V - 3Ø

520

600

600

18,000

400 ~ 500

2

Aluminum

 

LG3450

240V - 3Ø

451

450

 

#4 ~ 4/0

Lugs

275

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JG3225

480V - 3Ø

226

250

225

14,000

#4 ~ 350

1

 

 

 

LG3600

240V - 1Ø

542

 

 

 

 

 

 

 

 

 

 

 

600

600

18,000

400 ~ 500

2

 

275

MQP175IV

LG3601

208V - 3Ø

607

Aluminum

LG3602

240V - 3Ø

526

 

 

 

 

 

Lugs

 

 

 

 

 

 

 

 

 

KG3300

480V - 3Ø

263

400

300

14,000

250 ~ 500

1

 

375

 

MDL3700

208V - 3Ø

694

800

700

65,000

3/0 ~ 400

3

Aluminum

375

MQP200IV

 

 

 

 

 

 

 

 

 

LG3600

240V - 3Ø

601

600

600

18,000

400 ~ 500

2

275

Lugs

 

KG3300

480V - 3Ø

301

400

300

14,000

250 ~ 500

1

375

 

 

MQP250IV

 

 

 

Technical data for this unit TBD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NG31000

208V - 3Ø

1041

1,200

1,000

18,000

3/0 ~ 400

3

Aluminum

375

MQP300IV

 

 

240V - 3Ø

902

 

 

 

 

 

 

Lugs

 

 

LG3500

480V - 3Ø

453

600

500

14,000

3/0 ~ 350

2

275

 

 

 

NG31200

208V - 3Ø

1214

1,200

1,200

18,000

4/0 ~ 500

4

Aluminum

375

MQP350IV

 

 

 

 

 

 

NG31000

240V - 3Ø

1052

1,000

3/0 ~ 400

3

 

 

Lugs

 

 

LG3600

480V - 3Ø

526

600

600

14,000

4/0 ~ 500

2

275

 

 

MQP400V

 

 

 

Technical data for this unit TBD

 

 

 

 

RD316T33W

208V - 3Ø

1561

2,500

1,600

125,000

500 ~ 1000

4

Aluminum

550

MQP450VO

 

 

 

240V - 3Ø

1353

4

 

 

 

 

 

Lugs

 

 

MDL3700

480V - 3Ø

677

800

700

50,000

3/0 ~ 400

3

375

 

 

 

RD320T33W

208V - 3Ø

1735

2,500

2,000

125,000

#2 ~ 600

6

Aluminum

500

MQP500VO

 

 

 

 

 

 

240V - 3Ø

1503

1,600

125,000

500 ~ 1000

4

 

 

Lugs

 

 

 

 

 

 

 

 

 

 

 

 

MDL3800

480V - 3Ø

752

800

800

50,000

3/0 ~ 400

3

375

 

 

 

 

 

 

 

 

 

 

 

 

 

MQP550VO

 

 

 

Technical data for this unit TBD

 

 

 

MQP600VO

 

 

 

Technical data for this unit TBD

 

 

 

NOTES:

1.Refer to National Electric Code (NEC) for specific conductor sizes based on current and temperature ratings.

2.Lug sizes are given for standard circuit breaker setup. All lugs listed are made of aluminum and are compatible with both aluminum and copper conductors.

CONTINUED FROM PREVIOUS PAGE

PAGE 84 — INDUSTRIAL GENERATOR SETS — APPLICATION & INSTALLATION MANUAL — REV. #4 (09/07/07)

Page 84
Image 84
Multiquip MQP50IZ Appendix — Main-Linecircuit Breaker, FOR MQ POWER INDUSTRIAL GENERATORS cont, ABB or, Max. No, Type Of