AC ELECTRICAL CONNECTIONS
Emergency Standby Generator Systems (600 Volts and below) The National Electric Code (NEC) requires the
Generator Main Line Circuit Breaker
a)
b)Neutral Conductors – The ampacity of the neutral conductor is generally permitted to be equal to or greater than the calculated maximum
Sizing A Generator Main Line Circuit Breaker
Sizing a generator main line circuit breaker is typically the result of electrical engineering review of generator load schedules and design calculations for a feeder and its overcurrent device, keeping in mind that the primary purpose of the generator main line circuit breaker is to protect the feeder conductors as per the National Electric Code (NEC).
MQ Power offers several
It should be noted too, when sizing a main line circuit breaker, that feeder ampacity and overcurrent device ratings should be calculated by summing the total of load currents of all branch circuits being supplied by the
Field Installing A Generator Main Line Circuit Breaker
All work should be completed by qualified persons familiar with the installation, construction and operation of generator sets. All work should be completed in accordance with the National Electric Code (NEC), Uniform Building Code (UBC) and other state or local codes.
DO NOT attempt to field install a main line circuit breaker while the
When installing a main line circuit breaker NOT factory supplied by MQ Power, it is code required that the circuit breaker be UL listed. The overcurrent protective device should be installed with the correct voltage, current and
Once the circuit breaker has been properly sized and the appropriate cable and lugs have been determined, the circuit breaker should be mounted on the
Connection Of Generator Leads For Correct Voltage Output
It is required of the installer to connect the generator main stator leads