2.3.5 Wiring Outputs (continued)

This meter is capable of supplying 5 or 10 Vdc sensor excitation. The excitation output connection and location of S2 pin selection jumper are shown below.

Excitation is not available if Serial Communication (-C24) or Ethernet (-C4EI) or Low Voltage Power Supply (-DC) options are installed.

Figure 2.14

 

a) Excitation Output

b) Top View Location of S2

c) Top View Location of S2 on 1/8 DIN Compact Unit

Install jumpers according to the table below.

Table 2.4 Jumper Connections

 

 

Excitation Output

 

S2

 

 

 

A

 

B

 

 

 

 

 

 

10 V

Close

 

Open

 

 

5 V

Open

 

Close

 

 

 

 

 

Factory default is 10 V.

 

 

 