FILTER CONSTANT SUBMENU:

Press d Press b

Press d

14)Display flashes previous selection for Filter Constant.

15)Scroll though the available selections: 0001, 0002, 0004, 0008, 0016, 0032, 0064, 0128. - Default is 0004

16)Display shows STRD stored message momentarily only, if a change was made, otherwise press a to advance to IN.RD Input/Reading Submenu.

The Filter Constant Submenu allows the user to specify the number of readings stored in the Digital Averaging Filter.

For PID control select filter value 0001-0004. A filter value of 2 is approximately equal to 1 second RC low pass time constant.