FILTER CONSTANT SUBMENU:
Press d14) Display flashes previous selection for Filter Constant.
Press b15) Scroll though the available selections: 0001,0002,0004,
0008,0016,0032,0064 ,0128. - Default is 0004
Press d16) Display shows STRD stored message momentarily only, if a
change was made, otherwise press ato advance to IN.RD
Input/Reading Submenu.
The Filter Constant Submenu allows the user to specify the
number of readings stored in the Digital Averaging Filter.
For PID control select filter value 0001-0004. Afilter value of 2 is
approximately equal to 1 second RC low pass time constant.