ENTER INPUT TYPE MENU:
Press a1) Press a, if necessary, until CNFG prompt appears.
Press d2) Display advances to INPT Input Menu.
Press d3) Display flashes 0-0.1, 0-1.0, 0-10 or 0-20 (0 to 100 mV,
0 to 1 V, 0 to 10 V or 0 to 20 mA).
INPUT TYPE MENU:
Press b4) Scroll through the available selection of input ranges 0-0.1,
0-1.0, 0-10 or 0-20 to the selection of your choice.
Press d5) Display shows STRD stored message momentarily and then
advances to the RT1BRatiometric Operation Submenu.
Input Types: 100 mV 1 V 10 V 0 – 20 mA
Display: 0-0.1 0-1.0 0-10 0-20
RATIOMETRIC OPERATION SUBMENU:
Press d6) Display flashes previous selection of ENBL Enable or DSBL
Disable.
Press b7) Scroll through the available selection ENBL or DSBL
(flashing).
Press d8) Display shows STRD stored message momentarily and then
advances to RESO Input/Reading Resolution Submenu.
The Ratiometric operations are typically used for Strain gauge controller.
If your controller is configured as Process (Voltage and Current), set
RTIB to DSBL disable Ratiometric operations.
If ENBL Ratiometric operations Enabled was selected, the changes to
the excitation voltage will be compensated through Ratio measurement.
If DSBL Ratiometric operation Disabled was selected, any changes to
the excitation voltage will effect the output of strain gauge bridge and, as
a result, a reading of the controller.
INPUT/READING RESOLUTION SUBMENU:
Press a9) Display flashes previous selection of LO Low or HI High
resolution.
Press d10) Scroll through the available selection LO or HI (flashing).
Press d11) Display shows STRD stored message momentarily and then
advances to BUTN Button Selection Submenu.
If LO Low Resolution was selected the resolution of the display is 10 µV.
If HI High Resolution was selected the resolution of the display is 1 µV.
In case of High Resolution, the maximum input signal is 10 mV.
18