37
ENTER OUTPUT 1 MENU:
Press a1) Press a, if necessary, until CNFG prompt appears.
Press d2) Display advances to INPT Input Menu.
Press a3) Press a, if necessary, until display advances to OUT1 Output
1 Menu.
Press d4) Display advances to SELF Self Submenu.
SELF SUBMENU:
The Self Option allows the output of the instrument to be controlled manually
from the front panel.
Press d5) Display flashes the current setting of Self, ENBL Enabled or
DSBL Disabled.
Press b6) Press the bbutton to select between Enable and Disable.
Press d7) If Self ENBL Enabled was selected, display shows STRD
stored message momentarily and then advances to the next
menu (Output 1 setting is completed).
On the Run Mode display shows MXX.X The output is now
under the direct control of the operator and can be adjusted in
the Run Mode (M00.0 to M99.9), by pressing the band c
buttons, where Mcalls for manual (Self) control. For example,
setting of M50.0 of an analog output of 0 to 10 Vdc would
produce roughly 5 Vdc at the output.
8) If Self DSBL Disabled was selected, display shows STRD
stored message momentarily and then advances to ooLO
Minimum/Percent Low Submenu of Output 1 Menu.
There is a shorter way to Enable or Disable SELF Mode. From
a Run Mode press d and then press a. SELF Mode is Enabled
now. Press bor c to display MXX.XTo Disable SELF press d
and then press a. Display goes to the Run Mode. SELF Mode
is Disabled now.
MINIMUM/PERCENT LOW SUBMENU:
Specify in percent, the minimum value (0000) for control output. If the output is
analog proportional (Current or Voltage), then the minimum voltage or current, in
percent, is specified. If the output is time proportional (Relay, SSR or Pulse),
then the minimum duty-cycle, in percent, is specified.
Press d9) Display flashes 1st digit of previous “Percent Low” setting.
Press b& c10) Use band cbuttons to enter a new value for “Percent Low”.
Press d11) Display shows STRD stored message momentarily and then
advances to ooHI Maximum/Percent High Submenu.