Example 3:

Output 1 = Analog Output (Alarm 1 disabled), Setpoint 1 = 300, Output 2 = Relay, Setpoint 2 = 200

Alarm 1 & 2 Setup: Deviation, Band, “ALR.H” = 10

Color Display Setup: “N.CLR” = Green, “1.CLR” = Amber, “2.CLR” = Red

Display Colors change sequences:

AMBER

 

 

AMBER

AMBER

 

 

GREEN

 

AMBER

---------------•

•------ ------

--------------------------------•

------ -------•

----------------•

0

190

200

210

290

300

310

 

Alarm 1 is designed to monitor the Process Value around the Setpoint 1. Alarm 2 is designed to monitor the Process Value around the Setpoint 2. If Analog Output Option board is installed (Alarm 1 is disabled), only Alarm 2 is active and only two colors are available.

Example 4:

Output 1 = Relay, Setpoint 1 = 200

Output 2 = Relay, Setpoint 2 = 200

Alarm 1 Setup: Deviation, Band, “ALR.H” = 20

Alarm 2 Setup: Deviation, Hi/Low, “ALR.H” = 10, “ALR.L” = 5

Color Display Setup: “N.CLR” = Green, “1.CLR” = Amber, “2.CLR” = Red

Display colors change sequences:

AMBER

 

RED

 

GREEN

GREEN

RED

 

 

AMBER

 

----------------

•-------------

•--------------

•-------------

 

0

180

195

200

210

220

 

Reset: The instrument automatically resets after the last menu of the Configuration Mode has been entered. After the instrument resets, it advances to the Run Mode.