3.2.12 Output 2 Menu

Output 2 and Alarm 2 share the same contacts on the rear panel connector. If Alarm 2 is Enabled, Output 2 is automatically Disabled.

It is required that you put the controller in the Standby Mode for any configuration change other than Set Points & Alarms.

Figure 3.10 Flow Chart for Output 2 Menu

ENTER OUTPUT 2 MENU:

Press a

Press d

Press a

Press d

1)Press a, if necessary, until CNFG prompt appears.

2)Display advances to INPT Input Menu.

3)Press a, if necessary, until Display advances to OUT2 Output 2 Menu.

4)Display advances to CTRL Control Type Submenu.

CONTROL TYPE SUBMENU:

Press d

Press b

Press d

3)Display flashes ON.OF On/Off, or PID PID.

4)Scroll through the available selections: “ON.OF” or “PID”.

5)Display shows STRD stored message momentarily and then advances to AçTN only, if it was changed, otherwise press ￿ to advance to AçTN Action Type Submenu.

The ON.OF control is a coarse way of controlling the Process. The “Dead Band” improves the cycling associated with the ON.OF control. The PID control is best for processes where the set point is continuously changing and/or tight control of the Process Variable is required.

43