CYCLE TIME SUBMENU:
Press d15) Display flashes 1st digit of the previous “Cycle Time” value.
Press b& c16) Press band cbuttons to enter a new “Cycle Time” value
(1 to 199 seconds).
Press d17) Display shows STRD stored message momentarily and then
advances to RAMP only, if it was changed, otherwise press ato
advance to RAMP Ramp Value Submenu.
Acycle time selected between 1 to 199 seconds indicates the total On/Off time
of each proportional cycle.
For example, a 15 second cycle time means that every 15 seconds the output
will turn on for part or all of the cycle.
For Relay Control Outputs, do not select a cycle time of less than 7 seconds or
the relays’ lifetime will be shortened. For a cycle time of less than 7 seconds
select SSR or DC pulse. Use an external SSR with the DC pulse option for
higher current (higher than 1 Amp).
The DEADBAND Submenu will only appear if the ON/OFF was selected
from the "Control Type" Submenu.
DEADBAND SUBMENU:
Press d18) Display flashes 1st digit of the previous “Dead Band” value.
Press b& c19) Press band cbuttons to enter a new “Dead Band” value.
Press d20) Display shows STRD stored message momentarily and then
advances to RAMP only, if it was changed, otherwise press ato
advance to RAMP Ramp Value Menu.
Dead Band units are the same as Proportional Band units.
The Dead Band or neutral zone is the number of counts around the set
point which the Process Variable must pass above or below the set point,
before the output changes state.
45