ANALOG OUTPUT ENABLE/DISABLE SUBMENU:
Press b
Press d
5)Scroll though the available selection until ENBL displays to use Analog Output Retransmission (output proportional to the input signal).
6)Display shows STRD stored message momentarily and then
advances to CURR or VoLT Submenu only if it was changed, otherwise press a to advance to CURR or VoLT Current/Voltage Submenu.
If DSBL Analog Output Disabled was selected, all submenus of Analog Output Menu will be skipped and the meter will advance to ALR2 Alarm 2 Menu. If ENBL Analog Output Enabled was selected, Output 1 would be automatically Disabled, and reassigned as Analog Output.
CURRENT/VOLTAGE SUBMENU:
Press d
Press b
Press d
READING 1:
7)Display flashes CURR Current or VoLT Voltage.
8)Scroll through the available selection: Current or Voltage (Example VoLT ).
9)Display shows STRD stored message momentarily and then advances to RD1 Submenu only if it was changed, otherwise press a to advance to RD1 Reading 1 Submenu.
Press d
Press b & c
Press d
OUT 1:
Press d
Press b & c
Press d
READING 2:
Press d
Press b & c
Press d
OUT 2:
Press d
Press b & c
Press d
10)Display flashes 1st digit of previous “Reading 1” value.
11)Enter “Reading 1” value. (Example 0000)
12)Display advances to OUT.1 Out 1 Submenu.
13)Display flashes 1st digit of previous “Out 1” value.
14)Enter “Out 1” value. (Example 00.00)
15)Display advances to RD!2 Reading 2 Submenu.
16)Display flashes 1st digit of previous “Reading 2” value.
17)Enter “Reading 2” value. (Example 9999)
18)Display advances to OUT.2 Out 2 Submenu.
19)Display flashes 1stt digit of previous “Out 2” value.
20)Enter “Out 2” value. (Example 10.00)
21)Display advances to the ALR2 Alarm 2 Menu.
The above example is for 0 - 10 V of the entire range of the Process Input and Analog Output. For 0 - 20 mA output you need to set “Analog Type” to Current and OUT 2 to 20.00.
31