Panasonic CU-KS18NKUA, CU-KS12NK1A service manual Table, Be sure to completely insert the hex, Fig

Models: CS-KS18B4UW & CZ-18BT1U CS-KS12NB41 & CZ-18BT1U CU-KS12NK1A CU-KS18NKUA

1 136
Download 136 pages 28.94 Kb
Page 112
Image 112
Be sure to completely insert the hex

(4)With the “Lo” knob of the manifold valve open, run the vacuum pump. The operation time for the vacu- um pump varies with tubing length and the capacity of the pump. The following table shows the amount of time for evacuation:

Table 6

Required time for evacuation when

26.4 gal/h (100 liter/h) vacuum pump is used

If tubing length is

If tubing length is

less than 33 ft. (10 m)

more than 33 ft. (10 m)

 

 

10 min. or more

15 min. or more

 

 

NOTE

To prevent other refrigerants from being mistakenly charged to units which use R410A, the size of the charge port on the service valve is different from the one for other refrigerant types. For servicing such as recharging, the specified charging hose, manifold and vacuum pump adapter (with reverse flow prevention) for R410A must be used.

NOTE

(5) With the vacuum pump still running, close the “Lo”

The required time in Table 6 is calculated based on the

knob of the manifold valve. Then stop the vacuum

assumption that the ideal (or target) vacuum condition

pump.

is around 0.193 psi (10 mmHg abs.).

(6) With the hex wrench, turn the valve stem on the

 

narrow tube service valve counter-clockwise by

90° (1/4 turn)

90 degrees (1/4 turn) for 10 seconds, and then turn

Narrow tube

 

the stem clockwise to close it again. (Fig. 28)

Hex wrench

 

 

CAUTION

Be sure to completely insert the hex

Wide tube

 

 

wrench before attempting to turn the valve.

(7) Leak test all joints at the tubing (both indoor and outdoors) with

 

soapy water. Bubbles indicate a leak. Tighten the joint more

 

when leaks, then check if there is no leak. Be sure to wipe off the

Valve cap

soap with a clean cloth.

Vacuum hose to manifold valve

Fig. 28

 

(8)With the hex wrench, turn the wide tube service valve stem counter-clockwise to fully open the valve.

(9)Turn the narrow tube service valve stem counter-clockwise to fully open the valve.

(10)Loosen the vacuum hose connected to the wide tube service port slightly to release the pressure. Then, remove the hose.

CAUTION

This may cause the refrigerant gas to leak. In order to avoid this, take off the hose quickly.

(11)Fasten the valve cap on the wide tube service port securely with an adjustable wrench or box wrench. Next, mount the valve cap on the service valve and tighten it to 170 lbs·in (200 kgf·cm) with a torque wrench. This process is very important to prevent gas from leaking from the system.

(12)Test run the air conditioner. (See next page.)

(13)While the air conditioner is running, apply liquid soap to check for any gas leaks around the service valves or caps.

(14)If there is no leakage, stop the air conditioner.

(15)Wipe off the soap on the tubing.

This completes air purging with a vacuum pump and the air condi- tioner is ready for actual operation.

24

Page 112
Image 112
Panasonic CU-KS18NKUA Table, Be sure to completely insert the hex, wrench before attempting to turn the valve, Fig