Panasonic CS-KS18B4UW & CZ-18BT1U Air Purging, Taping the Tubes, Finishing the Installation, Fig

Models: CS-KS18B4UW & CZ-18BT1U CS-KS12NB41 & CZ-18BT1U CU-KS12NK1A CU-KS18NKUA

1 136
Download 136 pages 28.94 Kb
Page 111
Image 111
5-6. Taping the Tubes

5-6. Taping the Tubes

(1)At this time, the 2 refrigerant tubes (and electrical wire if local codes permit) should be taped together with armoring tape. The drain hose may also be included and taped together as 1 bundle with the tubing.

(2)Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn. (Fig. 25)

(3)Clamp the tubing bundle to wall, using 1 clamp approx. every 47" (120 cm).

NOTE

Do not wind the armoring tape too tightly, since this will decrease the heat insulation effect. Also, be sure the con- densation drain hose splits away from the bundle and drips clear of the unit and the tubing.

5-7. Finishing the Installation

After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering. (Fig. 26)

6. Air Purging

Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely.

pressure in the system rises

operating current rises

cooling (or heating) efficiency drops

moisture in the air may freeze and block capillary tubing

water may lead to corrosion of parts in the refrigerant system

Air Purging with a Vacuum Pump (for Test Run)

(1)Check that each tube (both narrow and wide tubes) between the indoor and outdoor units have been proper- ly connected and all wiring for the test run has been completed. Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage.

(2)Using an adjustable wrench or box wrench, remove the valve caps from the service valve on both narrow and wide tubes.

(3)Connect a vacuum pump and a manifold valve (with pressure gauges) to the service port on the wide tube service valve. (Fig. 27)

 

Clamp

Insulated tubes

Drain hose

Apply putty here

Fig. 25

Tubing

Fig. 26

Indoor unit

Outdoor unit

Manifold valve 5-7. Finishing the Installation (Exclusively for R410A)

Pressure

Lo

Hi

gauge

 

 

CAUTION

CAUTION

The service port on the wide tube service valve uses a Schrader core valve to access the refrigerant system. The valve core is similar to those used in automobile tires. Therefore, be sure to use a vacuum hose connector which has a push-pin inside.

Be sure to use a manifold valve for air purging. If it is not available, use a stop valve (field supply) for this purpose. The “Hi” knob of the manifold valve must always be kept closed.

Charging hose (Exclusively for R410A)

6. Air PurgingAir Purging with a Vacuum Pump (for Test Run)Manual background Vacuum pump adapter (Exclusively for R410A)

(with reverse flow prevention)

Vacuum pump

Fig. 27

23

Page 111
Image 111
Panasonic CS-KS18B4UW & CZ-18BT1U, CU-KS18NKUA, CU-KS12NK1A Air Purging, Taping the Tubes, Finishing the Installation, Fig