 How to Test Run the Air Conditioner

Fig. 11 How to Test Run the Air Conditioner

After turning on the power of the air conditioner, use the remote controller and follow the steps below to conduct the test run.

(1) Set the remote controller in Test Run mode. (Fig. 9)

a)Press and hold the NIGHT SETBACK button and the 1HR. TIMER button.

b)Then press and hold the ACL (Reset) button with a pointed object such as the tip of a pen. After 5 seconds, release the ACL button first.

c)Then release the NIGHT SETBACK and 1HR. TIMER buttons.

d)Manual background appears and “oP-1” blinking in the remote controller clock display area. (Fig. 10)

(2)Start Cooling mode test run by pressing the ON/OFF operation button of the remote controller. (Fig. 9)

‡This starts the fan producing uncooled forced air with the 3 indicator lamps (OPERATION lamp, TIMER lamp, and HIGH POWER lamp) on the main unit blinking. (Fig. 11)

‡After 3 minutes, the system shifts into cooling operation, and cool air will start to be felt. Cooling mode test run is unaffected by the room tempera- ture.

(3)Press the ON/OFF operation button of the remote controller again to stop the test run. (Fig. 9)

(4)Finally press the ACL (Reset) button of the remote controller to release it from Test Run mode to return to normal mode. (Fig. 9)

‡Manual background ” and “oP-1” will disappear from the remote controller clock display area.

NOTE

Troubleshooting:

In the event that the green OPERATION lamp is blink- ing upon powering up the system, an error condition exists. In this case, refer to the self-diagnostics proce- dure which can be seen by opening the air-intake grille.

IMPORTANT

After the test run is completed, be sure to press the ACL (Reset) button to return to normal mode. The air conditioner will not operate correctly if this is not done.

ON/OFF Manual background operation button

NIGHT SETBACK button

1 HR.TIMER button

ACL (Reset)

SENSOR button

button

 

 

Fig. 9

Fig. 10

OPERATION button

OPERATION lamp

Manual background TIMER lamp

Manual background HIGH POWER lamp

REMOTE CONTROL receiver

Fig. 11