Panasonic CS-KS12NB41 & CZ-18BT1U Recharging, Never charge a large amount, Example, Fig

Models: CS-KS18B4UW & CZ-18BT1U CS-KS12NB41 & CZ-18BT1U CU-KS12NK1A CU-KS18NKUA

1 136
Download 136 pages 28.94 Kb
Page 66
Image 66
(5) Recharging

(5) Recharging

Be sure to charge the specified amount of refrigerant in liquid state using the service port of the wide tube service valve. The proper amount is listed on the unit's nameplate.

When the entire amount cannot be charged all at once, charge gradually while operating the unit in Cooling Operation.

Never charge a large amount

CAUTION

of liquid refrigerant at once to the unit. This may cause damage to the compressor.

When charging with a refrigerant cylinder, use an electronic scale for charging refrigerant. In this case, if the volume of refrigerant in the cylinder becomes less than 20% of the fully-charged amount, the composition of the refrigerant starts to change. Thus, do not use the refrigerant if

the amount in the charging cylinder is less than 20%.

Also, charge the minimum necessary amount to the charging cylinder before using it to charge the air conditioning unit.

Example:

In case of charging refrigerant to a unit requiring

1.68lb. (0.76 Kg) using a capacity of a 22 lb. (10 Kg) cylinder, the minimum necessary amount for the cylinder is:

1.68+ 22 Never charge a large amount 0.20 = 6.08 lb. (0.76 + 10 Example: 0.20 = 2.76 Kg)

For the remaining refrigerant, refer to the instructions of the refrigerant manufacturer.

If using a charging cylinder, transfer the specified amount of liquid refrigerant from the refrigerant cylinder to the charging cylinder.

Prepare an evacuated charging cylinder beforehand.

CAUTION

To prevent the composition

 

of R410A from changing, never bleed the refrigerant gas into the atmosphere while transferring the refrigerant. (Fig. 3)

Do not use the refrigerant if the amount in the charging cylinder is less than 20%.

Configuration and characteristics of cylinders

Valve

Liquid

Single valve

Charge liquid refrigerant with cylinder in up-side-down position.

Fig. 1

Valve

Liquid

Single valve (with siphon tube)

Charge with cylinder in normal position.

Fig. 2

To prevent the compositionConfiguration and characteristics of cylinders NO!

Charging

cylinder

 

Liquid

Open

Refrigerant

 

cylinder

Fig. 3

66