(3) Installation procedure

(3) Installation procedure

CU-KS12NK1A

1. Air Intake Baffle

(1) Left side

1.Remove the front panel from the unit.

2.Remove the panel side L, and drill 2 holes of ø1/4 inch (6.5 mm) at the prescribed position.

3.Install the windbaffle on the unit using field supply bolts and nuts.

4.Recommended bolts to be used are 15/64" (M6 ISO standard), and the recommended length of the bolts is between 19/32 – 25/32 inch (15 – 20 mm).

5.Use washers and spring washers to tightly fasten the windbaffle to the unit.

(2) Right side

1.Remove the front panel from the unit.

2.Use 2 preholes on the panel side R to install the baffle plate.

3.Remove the panel side R from the unit by removing the screws. These screws are used in step 4 below.

4.Put (sandwich) the windbaffle between the unit and the panel side R, then install the windbaffle on the unit using the above screws. Be careful not to damage the screw holes.

Panel front

Panel side R

Panel side L

2.Air Discharge Baffle

1.Remove the panels front, side L and R from the unit and drill 4 holes of ø1/4 inch (6.5 mm) at the prescribed positions.

2.Install the windbaffle on the unit using field supply bolts and nuts.

3.Recommended bolts to be used are 15/64" (M6 ISO standard), and the recommended length of the bolts is between 13/32 – 19/32 inch (10 – 15 mm).

4.Use washers and spring washers to tightly fasten the windbaffle to the unit.

Panel side R

Panel front

Panel side L

Fig. 5h

Fig. 5i

NOTE

In order to prevent contact of the bolts and heat exchanger and other parts inside the unit, install the windbaffle using bolts from inside the unit and fasten the bolts with nuts from outside the unit.

When the windbaffle is installed on the unit, the unit has higher wind resistance. In order to prevent the unit from falling over, anchor the legs of the unit using anchor bolts (or similar method).