Patton electronic user manual Cited in section De-activating the Model 3196RC on

Models: 3196RC

1 93
Download 93 pages 46.66 Kb
Page 71
Image 71

Model 3196RC T-DAC User Manual

5 • Troubleshooting and maintenance

 

 

Introduction

This chapter describes troubleshooting and fault analysis that can be performed by the operator. If you require more help, refer to chapter 6, “Contacting Patton for assistance” on page 85. Refer to table 7 for a list of com- mon symptoms and suggested remedies.

Note The following information assumes that there is only one failure involving the Model 3196RC and that if you perform the corrective action listed, it will solve the problem. If you are unable to correct a failure, refer to chapter 6, “Contacting Patton for assistance” on page 85.

Note When removing the 3196RC from the chassis, follow the procedures

 

cited in section “De-activating the Model 3196RC” on page 69.

Note When re-inserting the 3196RC into the chassis, please follow the pro-

 

cedures cited in section “T-DAC blades installation” on page 25.

 

Table 7. Symptoms

 

 

Problem

Corrective Action

 

 

POWER LED (green)

To verify that power is being supplied to the Model 3196RC via the CPCI chassis power

is extinguished

bus: verify that at least one chassis power supply module is installed in the chassis and func-

 

tioning normally.

POWER LED (green) is

The 3196RC has detected a power failure on a power bus. There may be a problem with

flashing

the CPCI chassis power system which feeds the Model 3196RC such as a failed power sup-

 

ply module in the chassis. The Model 3196RC will function normally with one power supply.

 

Inspect the power supplies in the CPCI chassis to identify and replace the failed power sup-

 

ply module. If no failed power supply is found, or if the POWER LED continues flashing, con-

 

tact Patton Technical Support to determine if the T-DAC should be replaced.

 

 

CPU FAIL LED (red) is lit

CPU is unable to load the software from FLASH to RAM for operation. As soon as possible,

 

remove the Model 3196RC from the CPCI chassis, wait 30 seconds, then re-insert the

 

Model 3196RC into the CPCI chassis and see if the problem disappears. If the CPU FAIL

 

LED remains lit after the Model 3196RC completes the power-up cycle, contact Patton Tech-

 

nical Support to determine if the T-DAC needs to be replaced.

ALARM LED (yellow) is

Indicates The 3196RC has detected a minor or major alarm condition.

lit

 

 

 

SYSTEM LED (green) is

The Model 3196RC is not functioning properly. As soon as possible, remove the Model

not flashing

3196RC from the CPCI chassis, wait 30 seconds, then re-insert the Model 3196RC into the

 

CPCI chassis and see if the problem disappears. If the SYSTEM LED remains lit after the

 

Model 3196RC completes the power-up cycle, contact Patton Technical Support to deter-

 

mine if the T-DAC needs to be replaced.

ETHERNET LED (green)

A valid Ethernet link has not been detected. Verify that the Model 3196RC is connected

is extinguished

by means of an Ethernet cable to an Ethernet hub, switch, or workstation and that both

 

ends of the cable are plugged in.

 

Verify that the hub, switch, or workstation is powered on.

 

Verify that the correct cable is being used—either a straight through or cross-over cable

 

depending on whether you are connecting to a workstation (PC), hub, or switch.

 

Replace the Ethernet cable. If the problem still exists, contact Patton Technical Support to

 

determine if the T-DAC should be replaced.

 

 

Introduction

71

Page 71
Image 71
Patton electronic user manual Cited in section De-activating the Model 3196RC on