1.The output of the UPS is a separately derived source. Output neutral is bonded to equipment ground through the main bonding jumper. Refer to NEC Article 250 and local codes for proper grounding practices.

2.Your battery cabinet operating environment must meet the size and weight requirements shown in Table A:

Table A. Equipment Weight and Point Loading (on casters)

(4 leveling feet are provided)

 

Weight

Point Loading

Component

Kg (lb)

Kg (lb)

Series 685-J14

869 (1915)

4 at 217 (479)

 

 

 

Series 685-J17

1111 (2450)

4 at 278 (613)

 

 

 

Series 1085-J27

1429 (3150)

8 at 179 (394)

 

 

 

Series 1085-J31

1588 (3500)

8 at 199 (438)

 

 

 

Series 1085-J37

1708 (3765)

8 at 214 (471)

 

 

 

Series 1085-J47

2178 (4800)

8 at 272 (600)

3.The basic environmental requirements for operation of the battery system are:

Ambient Temperature Range:

10---

40˚C (50---

104˚F)

Recommended Operating Range:

20---

25˚C (68---

77˚F)

Maximum Relative Humidity:

95% noncondensing

4.Use Class 1 wiring methods (as defined by the NEC) for control wiring. Install the control wiring in separate conduit from the power wiring. The wire should be rated at 24 volts, 1 amp minimum.

5.Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is computed at 1.8 volts per cell.

6.The battery wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of nominal DC voltage at rated battery current.

7.A battery disconnect switch is recommended, and may be required by NEC or local codes when batteries are separately located. The battery disconnect switch may be supplied as an accessory, and should be installed between the battery and the UPS.

8.If the conductors used for DC input from the battery cabinet(s) to the UPS are those provided by the UPS manufacturer, and the UPS and battery cabinet are manufactured by the same supplier, then it is acceptable if they do not meet the noted minimum conductor sizes.

Table B. External Ground Wire Requirements for Battery Cabinets

 

 

 

 

Integral

 

Tool Size

Torque

UPS

Battery

Battery

# of

or

Wire Size

Battery

N-M

Model

Series

Type

Cabinets

Separate

Battery

Cabinet

(lb-in)

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

all

685 or 1085

all

all

all

1/0

7/16I slot

5.6 (50)

 

 

 

 

 

 

 

 

A---2

Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets

 

Installation Manual 164201408 Rev. P00 053002