To Electrically Connect Separate Battery Cabinets to the UPS:

1.All battery cabinets will arrive at your site with each battery connection string electrically disconnected. If you are installing more than one battery cabinet, perform Steps 2 through 6 for each cabinet. Battery cabinet #1 (the left-hand cabinet) will be the only cabinet directly connected to the UPS.

WARNING:

LETHAL VOLTAGE WILL BE PRESENT WHEN PERFORMING THE REMAINING

STEPS IN THIS SECTION AND SUBSEQUENT SECTIONS.

2.After making sure that all battery breakers are in the OFF position, connect the string of battery trays together by mating the loose red connector from each tray to the fixed black connector mounted on the front edge of the tray above it (see Figure 10 for Series 685 and Figure 13 for Series 1085 for location of all items discussed in this section).

3.Find the red (positive) and black (negative) cables supplied coiled inside the cabinet. These cables are provided half-stripped to facilitate attaching to the lugs in the cabinet. Use double pole compression lugs to secure the wires to the unit terminal blocks.

4.Remove the cable tie securing the battery breaker sensing cable.

5.Locate the battery breaker sensing cable in the right-hand battery cabinet. Route this connector into the cabinet to the immediate left and mate with the matching connector in the bottom of that cabinet. Connect all battery cabinets together this way.

6.Repeat Steps 2 through 5 for each battery cabinet to be joined.

7.Route cables from positive (+) and negative (---) terminals in the bottom of battery cabinet #1 through conduit (top or bottom entry) to terminals E4 and E5 of the UPS cabinet. See Figure 10 or Figure 12 for location of positive (+) and negative (---) terminals.

a.Refer to Appendix A, Table C to size wire for connecting the battery cabinets to the remotely located UPS cabinet.

b.See Drawing 164201408---1 in Appendix A for Series 685 Battery Cabinet top or bottom conduit landing locations.

c.See Drawing 164201408---2 in Appendix A for Series 1085 Battery Cabinet top or bottom conduit landing locations.

d.See Installation Manual 164200253 for Powerware 9350 30---80 kVA top or bottom conduit landing locations.

e.See Installation Manual 164200292 for Powerware 9350 100---160 kVA top or bottom conduit landing locations. The conduit landing plates are removable to add conduit landing holes as required. The conduit landing plates should be removed when holes are added to keep metal particles from falling inside the battery cabinet.

f.Refer to Chapter 5, Table C for remote battery disconnect circuit breaker information.

 

 

 

Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets

25

Installation Manual 164201408 Rev. P00 053002

 

 

Page 31
Image 31
Powerware 1085, 685 installation manual To Electrically Connect Separate Battery Cabinets to the UPS