Table C. External Wiring Requirements
NOTE: All specified wire sizes are 90_C rated copper minimum | Battery Cabinet | UPS Cabinet | ||||||||
|
|
|
|
|
|
|
|
|
| |
UPS | Battery |
|
| Integral | Wire |
| Torque |
| Torque | |
Battery | # of | Size |
|
| ||||||
Series/ | Cabinet | or | Tool Size | Tool Size | ||||||
Type* | Cabinets | UPS to | ||||||||
Model | Series | Separate |
|
| ||||||
|
|
|
|
| Battery |
|
|
|
| |
160/125 | 685 | H20 | 2 | Integral | Supplied | 3/8I hex | 42.4 | 3/8I hex | 42.4 | |
(375) | (375) | |||||||||
|
|
|
|
|
|
|
| |||
160/125 | 685 | H20 | 2 | Separate | 300 | 3/8I hex | 42.4 | 3/8I hex | 42.4 | |
kcmil | (375) | (375) | ||||||||
|
|
|
|
|
|
| ||||
|
| B27, B31, |
|
|
|
|
|
|
| |
160/125 | 1085 | B37, B47, | 2, 3, or 4 | Integral | Supplied | 3/8I hex | 42.4 | 3/8I hex | 42.4 | |
H30, H40, | (375) | (375) | ||||||||
|
| H50 |
|
|
|
|
|
|
| |
|
| B27, B31, |
|
|
|
|
|
|
| |
160/125 | 1085 | B37, B47, | 2, 3, or 4 | Separate | 300 | 3/8I hex | 42.4 | 3/8I hex | 42.4 | |
H30, H40, | kcmil | (375) | (375) | |||||||
|
| H50 |
|
|
|
|
|
|
| |
160/150 | 685 | H20 | 2 | Integral | Supplied | 3/8I hex | 42.4 | 3/8I hex | 42.4 | |
(375) | (375) | |||||||||
|
|
|
|
|
|
|
| |||
160/150 | 685 | H20 | 2 | Separate | 300 | 3/8I hex | 42.4 | 3/8I hex | 42.4 | |
kcmil | (375) | (375) | ||||||||
|
|
|
|
|
|
| ||||
|
| B27, B31, |
|
|
|
|
|
|
| |
160/150 | 1085 | B37, B47, | 2, 3, or 4 | Integral | Supplied | 3/8I hex | 42.4 | 3/8I hex | 42.4 | |
H30, H40, | (375) | (375) | ||||||||
|
| H50 |
|
|
|
|
|
|
| |
|
| B27, B31, |
|
|
|
|
|
|
| |
160/150 | 1085 | B37, B47, | 2, 3, or 4 | Separate | 300 | 3/8I hex | 42.4 | 3/8I hex | 42.4 | |
H30, H40, | kcmil | (375) | (375) | |||||||
|
| H50 |
|
|
|
|
|
|
| |
160/160 | 685 | H20 | 2 | Integral | Supplied | 3/8I hex | 42.4 | 3/8I hex | 42.4 | |
(375) | (375) | |||||||||
|
|
|
|
|
|
|
| |||
160/160 | 685 | H20 | 2 | Separate | 300 | 3/8I hex | 42.4 | 3/8I hex | 42.4 | |
kcmil | (375) | (375) | ||||||||
|
|
|
|
|
|
| ||||
|
| B27, B31, |
|
|
|
|
|
|
| |
160/160 | 1085 | B37, B47, | 1, 2, 3, | Integral | Supplied | 3/8I hex | 42.4 | 3/8I hex | 42.4 | |
H30, H40, | or 4 | (375) | (375) | |||||||
|
|
|
|
|
| |||||
|
| H50 |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
| B27, B31, |
|
|
|
|
|
|
| |
160/160 | 1085 | B37, B47, | 1, 2, 3, | Separate | 350 | 3/8I hex | 42.4 | 3/8I hex | 42.4 | |
H30, H40, | or 4 | kcmil | (375) | (375) | ||||||
|
|
|
|
| ||||||
|
| H50 |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
| * BATTERY | TYPE | DESIGNATIONS: | B = | C&D, H = | HAWKER |
|
|
NOTE: The term “Separate” refers to battery cabinets that are not physically attached to the UPS, are wired with external contractor supplied wiring, and use a single overcurent protection and disconnect device located near the batteries.
The term “Integral” refers to battery cabinets that are physically attached to the UPS and the wiring between them is internal. The power wiring is supplied with the system, and they use the UPS battery switch as the battery isolation device.
The wire size rating for products up to and including the 160/160 are for the total battery supply. Since these UPS units can only land one wire per DC connection point, a common DC collector including an isolation device and overcurrent protection should be used. Refer to applicable national or local code requirements for your installation.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets | |
Installation Manual 164201408 Rev. P00 053002 |
|