Quadra-Fire QFP44 owner manual 6Termination Locations, A. Vent Termination Minimum Clearances

Models: QFP44

1 68
Download 68 pages 49.02 Kb
Page 27
Image 27
6Termination Locations

6Termination Locations

A. Vent Termination Minimum Clearances

A. Vent Termination Minimum Clearances WARNING

Fire Risk.

Maintain vent clearance to combustibles as speci ed.

DO NOT pack air space with insulation or other materials.

Failure to keep insulation or other materials away from vent pipe may cause overheating and re.

Direct Vent Gas, Wood or Fuel

Oil Termination

Manual background 20 in.Manual background

 

 

A

(508 mm)

18 in.

 

(minimum) to

 

 

 

 

Perpendicular

(457 mm)

 

 

Wall

 

B

 

(DV only)

 

 

 

Gas

Termination Manual backgroundManual backgroundManual backgroundManual backgroundManual background

24 in. min.

(610 mm)

Termination

Cap

Storm Collar

Manual background 20 in.Manual background (508 mm)

Lowest

Discharge

Manual background Opening

12

Horizontal overhang

Vertical wall

X

Termination Caps Staggered Height

A

Gas Termination

Wood or Fuel Oil Termination

B

6 in. (152 mm) min.

20 in. (508 mm) min.

Figure 6.2 Staggered Termination Caps

Direct Vent Gas, Wood or Fuel

Oil Termination

Wood, Gas or

Fuel Oil

Roof Flashing Manual background

Manual background Roof Pitch is X / 12

H (min.) - Minimum height from roof to lowest discharge opening.

Termination

 

 

 

 

20 in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(508 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(minimum) to

 

 

 

 

20 in. min. *

 

 

 

Perpendicular

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wall

 

 

 

 

 

 

(508 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(DV only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Roof Pitch

H (Min.) Ft.

Roof Pitch

H (Min.) Ft.

Flat to 6/12

 

1.0*

Over 11/12 to 12/12

4.0

Over 6/12 to 7/12

1.25*

Over 12/12 to 14/12

5.0

Over 7/12 to 8/12

1.5*

Over 14/12 to 16/12

6.0

Over 8/12 to 9/12

2.0*

Over 16/12 to 18/12

7.0

Over 9/12 to 10/12

2.5

Over 18/12 to 20/12

7.5

Over 10/12 to 11/12

3.25

Over 20/12 to 21/12

8.0

 

* 3 ft. minimum in snow regions

 

 

Termination Caps Same Height

*If using decorative cap cover(s), this distance may need to be increased. Refer to the installation instruc- tions supplied with the decorative cap cover.

Figure 6.3 Leveled Termination Caps

Figure 6.1 Minimum Height From Roof To Lowest Discharge Opening

Quadra-Fire • QFP44 • 4051-300 Rev M • 09/08

27