Deciding on where to install the product

3When air inlet and air outlet of the outdoor unit are blocked

Case 1: Obstacle on exhausting side is higher than the unit.(regardless of the height of obstacle on suction side)

The upper part of the outdoor unit is not blocked

(Unit: mm)

• When installing 1 outdoor unit • When parallel installing more than 2 outdoor units(*1)

300 or

more

1500 or

more

1500 or

more

300 or more

600 or 600 or more more

300 or

more

1500 or

more

1500 or

more

300 or more

––The backside block can not be higher than the outdoor unit. If the backside block is higher than the outdoor unit, arrange the outdoor unit higher than the backside block.

Case 2: Obstacle on exhausting side is lower than the unit.(regardless of the height of obstacle on suction side)

The upper part of the outdoor unit is not blocked

(Unit: mm)

• When installing 1 outdoor unit • When parallel installing more than 2 outdoor units(*1)

INSTALLATION

300 or

more

1500 or

more

1500 or

more

300 or

more

600 or 600 or more more

300 or

more

1500 or

more

1500 or

more

300 or more

PARTS

––The frontside block can not be higher than the outdoor unit. If the frontside block is higher than the outdoor unit, arrange the outdoor unit higher than the frontside block.

––(*1) When installing outdoor units paralleled, more than 600mm gap shall be left.

When front and rear side of the outdoor unit is toward the wall

1500 or more

600 or

3000 or

3000 or 3000 or more

 

more

more

more

40English