2Pipe installation condition may vary depending on the installation location. Therefore, use indoor and outdoor unit elbow pipe connector to install the pipe if necessary.

––Allowable pipe length: Maximum 75m

––Allowable pipe height difference: Maximum 30m

––Make sure that there are less than 10 bending points in a pipe.

CAUTION

If the pipe is lengthened, the performance of the unit is degraded, and the service life is shortened. Therefore, try to keep the pipe length as short as possible.

You must install 1 S-trap on the gas side pipe up to 6m of height difference.

If the height difference of the pipe exceeds 6m, install S-trap every 6m.