Connecting power and communication cable

This product uses the power for 380 V 50 Hz, 3-phase 4 wires. The indoor unit uses the power for 220 V 50 Hz, single-phase. The power cables for both units must be separated.

1Remove the cover of the electrical component on the outdoor unit.

2Connect the power cable (R, S, T, N) to the R, S, T, N of the terminal on the electrical component on the outdoor unit. (Power cable must be purchased separately.)

3When tightening the screw on the terminal block, apply appropriate tightening torque to assemble cables to the terminal.

4Install ELB [Earth Leakage breaker (for 4 wires)] for air conditioner. It must be selected according to the starting current of the compressor.

Indoor unit

Outdoor unit

Communication

terminal

1(L) 2(N)

F1 F2

F2 F1

R

S

T

N

Earth

 

Indoor-to-outdoor

 

 

 

 

 

 

unit connection wire

 

 

 

 

 

Distributing board

ELB for ELB for outdoor unit indoor unit

Earth

R

S

T

N

L

N

Earth

Power supply cable for outdoor unit

Power supply cable for indoor unit

INSTALLATION PARTS

English 59

Page 59
Image 59
Samsung AF0AKV3SAEENSG manual Connecting power and communication cable, Earth