Samsung AF0AKV3SAEENSG manual Storing refrigerant pipe

Models: AF0AKV3SAEENSG

1 80
Download 80 pages 33.41 Kb
Page 49
Image 49

Storing refrigerant pipe

To prevent foreign materials or water from entering the pipe, it is important to keep the refrigerant pipe sealed in clean and dry condition during installation. Apply correct sealing method depending on the environment.

Stored place

Stored time

Sealing type

Outside

Longer than one month

Pipe pinch

Shorter than one month

Taping

 

Inside

-

Taping

Refrigerant pipe brazing and safety information

Important information for refrigerant pipe work

Important information for refrigerant pipe work ––Make sure that there is no moisture inside the pipe.

––Make sure that there are no foreign materials and impurities in the pipe. ––Make sure that there is no leak.

––Make sure to follow the instruction when brazing and keeping the pipe.

Nitrogen flushing brazing

––Use nitrogen gas when brazing the pipes as shown in the picture.

––If you do not perform nitrogen flushing when brazing the pipes, oxide may form inside the pipe. It can cause the damage of the important parts such as compressor, valves.

––Adjust the flow rate of the nitrogen flushing with a pressure regulator to maintain 0.05m3/h or less.

––Wrap the bottom side of the service valve with a wet cloth and weld it as shown in the figure. Since water will evaporate during welding, pour some water time to time. If not, O-ring and packing inside the service valve may get damaged by a welding fire and cause critical leakage.

Brazing part

ø 6.35 (1/4”) copper pipe

Gas side

 

 

Stop valve

service valve

 

Nitrogen gas

Wet towel

 

 

 

 

 

 

Pressure regulator

Taping

 

 

 

 

Flowmeter

High pressure hose

 

 

 

 

 

 

Nitrogen gas

 

 

 

 

INSTALLATION PARTS

English 49

Page 49
Image 49
Samsung AF0AKV3SAEENSG manual Storing refrigerant pipe