Samsung AF0AKV3SAEENSG manual Pipe connection, Selecting refrigerant pipe

Models: AF0AKV3SAEENSG

1 80
Download 80 pages 33.41 Kb
Page 48
Image 48

Refrigerant piping work

Pipe connection

Indoor unit

Outdoor unit

Gas pipe

Liquid pipe

Gas

 

 

 

 

 

 

 

 

 

 

 

Liquid

pipe

 

 

 

 

 

 

 

 

 

 

pipe

 

 

 

 

 

 

Selecting refrigerant pipe

 

Model name

Liquid side (mm)

Gas side (mm)

 

AF80KV3SAEEX

Ø9.52

Ø19.05

 

AF0AKV3SAEEX

Ø9.52

Ø22.23

 

Temper grade and minimum thickness of the refrigerant pipe

 

 

 

 

 

Outer diameter [mm/(inch)]

Minimum thickness (mm)

Temper grade

 

Ø 6.35 (1/4)

0.7

 

INSTALLATION

Ø 9.52 (3/8)

0.7

 

Ø 25.40 (1)

1.0

 

 

Ø 12.70 (1/2)

0.8

C1220T-O (Soft)

 

Ø 15.88 (5/8)

0.8

 

 

Ø 19.05 (3/4)

1.0

 

 

Ø 22.23 (7/8)

0.9

 

PARTS

 

 

 

Ø 28.58 (1-1/8)

1.1

C1220T-1/2H (Semi-soft) or

 

 

Ø 31.75 (1-1/4)

1.1

 

C1220T-H (Soft)

 

Ø 38.10 (1-1/2)

1.35

 

 

 

Ø 44.45 (1-3/4)

1.6

 

 

Ø 50.80 (2)

2.0

 

48English