No.

Error

Meaning

Remarks

Code

16

E251

Error on discharge temperature sensor of

Check Discharge sensor Open / Short

compressor 1 (Short or Open)

17

E320

Error on OLP sensor (Short or Open)

Check OLP sensor Open / Short

18

E346

Error due to operation failure of Fan2

Fan2 error

19

E347

Motor wire of Fan2 is not connected

Fan2 error

20

E348

Lock error on Fan2 of outdoor unit

Fan2 error

21

E353

Error due to overheated motor of outdoor unit's

Fan2 error

Fan2

22

E355

Error due to overheated IPM of Fan2

Fan2 error

23

E378

Error due to overcurrent of Fan2

Fan2 error

24

E386

Over-voltage/low-voltage error of Fan2

Fan2 error

25

E387

Hall IC connection error of Fan2

Fan2 error

26

E389

V-limit error on Fan2 of compressor

Fan2 error

27

E391

Error due to DataFlash of Fan2

Fan2 error

28

E393

Output current sensor error of Fan2

Fan2 error

29

E396

DC voltage sensor error of Fan2

Fan2 error

30

E399

Heat sink temperature sensor error of Fan2

Fan2 error

31

E403

Compressor down due to freeze protection

Check Outdoor Cond.

control

32

E404

System stop due to overload protection control

Check Comp. when it start

33

E416

System stop due to discharge temperature

-

 

 

 

1. Check if the service valve is open

 

 

 

2. Check for refrigerant leakage(pipe

 

 

 

connections, heat exchanger) and

 

 

 

charge refrigerant if necessary

34

E422

Blockage detected on high pressure pipe

3. Check if there's any blockage on

 

 

 

refrigerant cycle(indoor unit/outdoor

 

 

 

unit)

 

 

 

4. Check if additional refrigerant has

 

 

 

been added after pipe extension

35

E425

Reverse phase or open phase

Check whether 3 phase is reversed or

opened.

 

 

 

36

E440

Heating mode restriction due to high air temperature

Heating

37

E441

Cooling mode restriction due to low air temperature

Cooling

38

E446

Error due to operation failure of Fan1

Fan1 error

INSTALLATION PARTS

English 71

Page 71
Image 71