Selecting the insulator of the refrigerant pipe

Insulate the gas pipe and liquid pipe by referring to the thickness of insulator for each pipe size.

The standard condition for indoor temperature is 30°C with humidity less than 85%. If the condition is out of this standard condition, use the pipe that is one grade thicker.

Pipe diameter (mm)

Minimum thickness of the insulator

Remarks

PE material

EPDM material

 

 

ø 6.35~ø 19.05

13

10

If the installation place has high

 

 

 

humidity (such as basement of a

ø 22.23~ø 31.75

19

13

building, seaside, near hot spring

 

 

 

ø 38.10~ø 44.45

25

19

or lake etc.) increase the minimum

 

 

 

-

32

25

thickness to next size up for each pipes.

Insulating refrigerant pipe

Pipe insulation

––Insulation of the gas and liquid pipes can be in contact with each other but they should not be pressing each other.

––When contacting the gas side and liquid side pipe, use thicker insulation.

Insulation

 

Insulation

 

Liquid pipe

Gas pipe

 

 

 

CAUTION

Make sure to install the insulation so that there is no gap or crack and use the adhesives on the connection part of it to prevent moisture from entering.

Wind the refrigerant pipe with insulation tape if it is exposed to outside sunlight. (When winding the insulation tape, make sure that the thickness of the insulator does not get any thinner.)

Install the refrigerant pipe respecting that the insulation does not get thinner on the bent part or hanger of pipe.

If the thickness of the insulation gets thinner, use additional insulation.

Additional

 

Hanger

insulation

 

 

a

Insulation for

 

refrigerant pipe

 

a x 3

 

 