Power supply and wire specification
| Model name |
|
|
|
| Indoor unit |
| Outdoor unit | ||||||
|
|
|
|
| AF80KV3SAEEN |
| AF80KV3SAEEX | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Power supply |
|
|
| Product |
|
| 220 - 240 V~ 50 Hz | 380 - 415 V 3N~ 50 Hz | ||||||
Power | Cooling |
|
|
| T1 |
| W | 520 W |
| 8000 W | ||||
|
|
| T3 |
|
| 520 W |
| 7600 W | ||||||
consumption |
|
|
|
|
|
|
|
| ||||||
Heating |
|
| - |
|
|
| W | - |
| - | ||||
Operationg | Cooling |
|
|
| T1 |
| A | 2.3 A |
| 12.5 A | ||||
|
|
| T3 |
|
| 2.3 A |
| 11.9 A | ||||||
current |
|
|
|
|
|
|
|
| ||||||
Heating |
|
| - |
|
|
| A | - |
| - | ||||
|
|
|
|
|
|
| ||||||||
Capacity of |
| Product |
|
|
| A | 30 |
| ||||||
circuit breaker |
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Thickness of ground wire |
|
|
| mm2 | 4.0 |
| ||||||||
Indoor and outdoor unit |
|
|
| mm2 | 0.75~1.5 |
| ||||||||
communication wire |
|
|
|
| ||||||||||
|
|
|
|
|
|
| ||||||||
|
|
|
|
| Type |
|
|
|
| At least equal to | At least equal to | |||
|
|
|
|
|
| Below | mm2 | 2.5 (Should be purchased | 2.5 (Should be purchased | |||||
Power wire | Product |
|
| 20m |
| separately) |
| separately) | ||||||
|
| 20m or | mm2 | 4.0 (Should be purchased | 4.0 | (Should be purchased | ||||||||
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
| over |
| separately) |
| separately) | |||
| Model name |
|
|
|
| Indoor unit |
| Outdoor unit | ||||||
|
|
|
|
| AF0AKV3SAEEN |
| AF0AKV3SAEEX | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Power supply |
|
|
|
| Product |
| 220 - 240 V~ 50 Hz | 380 - 415 V 3N~ 50 Hz | ||||||
|
|
| Cooling |
|
| T1 | W | 560 W |
| 11 900 W | ||||
Power consumption |
|
|
| T3 | 560 W |
| 9900 W | |||||||
|
|
| Heating |
|
| - | W | - |
| - | ||||
|
|
| Cooling |
|
| T1 | A | 2.5 A |
| 18.3 A | ||||
Operationg current |
|
|
| T3 | 2.5 A |
| 15.4 A | |||||||
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
| Heating |
|
| - | A | - |
| - | ||||
Capacity of circuit |
|
|
| Product |
| A | 30 |
| ||||||
breaker |
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Thickness of ground wire |
|
|
| mm2 | 4.0 |
| ||||||||
Indoor and outdoor unit |
|
|
| mm2 | 0.75~1.5 |
| ||||||||
communication wire |
|
|
|
| ||||||||||
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
| Type |
|
| At least equal to | At least equal to | ||||
|
|
|
|
|
|
| Below | mm2 | 2.5 (Should be purchased | 4.0 (Should be purchased | ||||
Power wire | Product |
| 20m | separately) |
| separately) | ||||||||
|
|
| 20m | mm2 | 4.0 (Should be purchased | 6.0 | (Should be purchased | |||||||
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
| or over |
| separately) |
| separately) |
INSTALLATION PARTS