Sanyo CH3082 Countermeasures against snow and wind, Precautions for Installation in a Snowy Area

Models: KHS3082 + CH3082 CH3682 CH3082 KHS3682 + CH3682

1 109
Download 109 pages 19.55 Kb
Page 84
Image 84

2-2-1. Installing the Unit in an Area with High Winds and in a Snowy Area

In locations with high winds, a wind-proof duct should be fitted and direct exposure to the wind should be avoided as much as possible. (Fig. 5e)

In regions with significant snowfall, the outdoor unit should be provided with a platform and snow-proof duct. (Fig. 5f)

Countermeasures against snow and wind

In regions with snow and strong wind, the following problems may occur when the outdoor unit is not provided with a platform and ducting:

a)The outdoor fan may not run and damage to the unit may occur.

b)There may be no air flow.

c)The tubing may freeze and burst.

d)The condenser pressure may drop because of strong wind, and the indoor unit may freeze.

2-2-2. Precautions for Installation in a Snowy Area

Air discharge

Air discharge

Air discharge

Air discharge

Fig. 5e

Outdoor unit

Duct

(1)The platform should be higher than the maximum snow depth. (Fig. 5g)

(2)The 2 anchoring feet of the outdoor unit should be used for the platform, and the platform should be installed beneath the air intake side of outdoor unit.

(3)The platform foundation must be firm and the unit must be secured with anchor bolts.

(4)In case of installation on a roof subject to strong wind, countermeasures must be taken to prevent the unit from being blown over.

Air Intake

 

 

 

 

unit

height

 

 

 

the

 

 

 

of

 

 

 

1/2

 

 

 

About

 

 

 

 

 

 

 

 

 

 

h

the

dept

w

thansno

 

igherm

 

um

 

H axi

 

m

 

Air Intake

Platform (foundation)

Fig. 5f

Without snow-

Without snow-

proof ducting

proof ducting

(Low platform)

(High platform)

Fig. 5g