8-3. Checking the Indoor and Outdoor Units
(1) Checking the indoor unit
No. | Control | Check items (unit operation) |
1 | Use the remote controller to operate the | • The rated voltage must be present between |
| unit in "TEST run" mode. To determine | • Connect a 5 k ohm resistor between |
| whether the mode is currently in | voltage at both ends is measured, approximately 12 to 15V DC must |
| "TEST run" mode, check the 4 indicator | be output and the multimeter pointer must bounce once every 8 |
| lamps on the unit. If all 4 are blinking, | seconds. |
| the current mode is "TEST run." | Or instead of measuring the voltage, you can insert an LED jig and |
|
| check that the LED flickers once every 8 seconds. |
If there are no problems with the above, then check the outdoor unit. | ||
For the "Test run" procedure, refer to the Appendix B "Installation Instructions". | ||
(2) Checking the outdoor unit |
| |
No. | Control | Check items (unit operation) |
1 Apply the rated voltage between outdoor | • The control panel LED (red) must illuminate. | |
| unit terminals L and N. |
|
2
If there are no problems with the above, then check the indoor unit.
Using the |
| |||||||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
TEST/MV : Compresses time to 1/60th (accelerates |
|
|
|
|
|
|
|
|
|
|
operation by 60 times faster than normal). |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| (TEST)/MV |
|
| COM |
44