Required space around the outdoor unit

If the wind-proof duct is used, the space shown below must be secured around the outdoor unit.

If the unit is used without the required space, a protective device may activate, preventing the unit from operating.

(1) Single-unit installation

Min. 39-3/8" or more

Min. 8" or more

Unit: inch

CAUTION

The top and both sides must remain open. If there are obstacles to the front and rear of the outdoor unit, the obstacle at either the front or rear must be no taller than the height of the outdoor unit.

(2)Multiple-unit installation Installation in lateral rows

More than 9-27/32"

More than 6"

 

than 8"

More than 9-27/32"

More

 

Unit: inch

CAUTION

The front and top must remain open.

The obstacles must be no taller than the height of the outdoor unit.

Installation in front-rear rows

Installation with intakes facing intakes or outlets facing outlets

More than 11-13/16"

More than 47-1/4"

Installation with intakes facing outlets

More than 78-3/4"

CAUTION

Unit: inch

The front and both sides must remain open.