7. FUNCTIONS
7-1. Operation Functions
Emergency operation
Emergency operation is available when the remote controller malfunctions, has been lost, or otherwise cannot be used.
To operate the system, press the OPERATION button, which is also used as the receiver, below the unit display. Each time this button is pressed, the OPERATION lamp changes color to indicate the type of operation. Select the desired type of operation.
COOL |
| HEAT |
| STOP |
|
| |||
(GREEN) |
| (RED) |
| (Lamp Off) |
•The set temperature is 4°F(2°C) below the detected room temperature in the case of cooling operation, and 4°F(2°C) above the room temperature in the case of heating operation. The flap and fan speed settings are AUTO.
AUTO cooling/heating operation
Selecting the operation mode
•When AUTO mode is selected, the microprocessor calculates the difference between the set temperature and the room temperature, and automatically switches to Cooling or Heating mode.
Room temp. Set temp. COOL Room temp. Set temp. HEAT
•As shown by the example in the figure below, with AUTO cooling/heating operation, the mode changes between Heating and Cooling mode according to changes in the relationship between the current room temperature and the set temperature.
Example
Example of operation in AUTO mode with the set room temperature at 74°F(23°C).
Room temp. |
|
|
|
|
| ||
|
| Zone A |
|
|
|
|
|
|
| Zone B |
|
|
|
|
|
Set temp. | 74 | Zone C |
|
|
|
|
|
Zone C |
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
| Zone B |
| More than |
| Within |
|
|
|
|
|
|
| ||
|
| Zone A |
| 1 hour |
| 1 hour |
|
|
| Compressor | ON | OFF | ON | OFF | ON |
| Operation mode |
| Cooling |
| Heating | Cooling |
SENSOR DRY
During DRY operation, the system adjusts the room temperature and fan speed according to the conditions in the room, in order to maintain a comfortable room environment.
SENSOR DRY operation
•DRY operation is as shown in the figure below.
Load
COOL zone
Azone
Bzone
Conditions are monitored at all times when the room temperature is below 59°F(15°C).
DRY A
The compressor operation frequency varies.
The indoor fan operates with 1/f fluctuation.
DRY B
The compressor operates at a low operating frequency. The indoor fan operates with 1/f fluctuation.
Monitor
•Monitoring operation takes place when the room temperature is below 59°F(15°C), or more than 5°F(3°C) below the set temperature.
•When the monitoring range is entered, the compressor stops, and the indoor fan operates with 1/f fluctuation.
NOTE
The Sensor Dry operation during the Low Ambient Cooling Mode (outside air temperature : 59°F(15°C) or lower) is as follows.
DRY A and DRY B
When room temperature rises above the set temperature, the compressor turns ON. When room temperature falls below the set temperature, the compressor turns OFF.
35