3GENERAL SET

Setting RS-485

Settings are required when the RS-485 terminals (A and B) are connected with a system controller or other devices.

1 Press the [MENU] button.

The MENU indicator lights up and the <MAIN MENU> is displayed.

MENU

2 Turn the jog dial to select “3.GENERAL

SET” and then turn the shuttle dial clockwise.

The <GENERAL SET> screen is displayed.

3 Turn the jog dial to select “4.RS-485 SET” and then turn the shuttle dial clockwise.

The <RS-485 SET> screen is displayed.

<RS-485 SET>

 

DATA SPEED

:

19200

STATUS INFO

:

OFF

ALARM INFO

:

OFF

ADDRESS

:

001

4 Turn the shuttle dial clockwise.

“19200” flashes for “DATA SPEED”.

<RS-485 SET>

 

DATA SPEED

: 19200

STATUS INFO

: OFF

ALARM INFO

: OFF

ADDRESS

: 001

5 Turn the jog dial to select the “DATA SPEED” setting and then turn the shuttle dial clockwise.

The cursor moves to “STATUS INFO”.

<RS-485 SET>

 

DATA SPEED

: 19200

STATUS INFO

: OFF

ALARM INFO

: OFF

ADDRESS

: 001

[Settings] (‹ indicates default setting)

Setting

Description

2400, 4800, 9600, ‹19200

Sets the data speed.

 

 

6 Turn the shuttle dial clockwise.

“OFF” flashes for “STATUS INFO”.

<RS-485 SET>

 

DATA SPEED

: 19200

STATUS INFO

: OFF

ALARM INFO

: OFF

ADDRESS

: 001

7 Turn the jog dial to select “STATUS INFO” and then turn the shuttle dial clockwise.

The cursor moves to “ALARM INFO”.

<RS-485 SET>

 

DATA SPEED

:

19200

STATUS INFO

:

OFF

ALARM INFO

:

OFF

ADDRESS

:

001

[Settings] (‹ indicates default setting)

Setting

Description

ON

Status information is transmitted.

 

 

‹OFF

Status information is not transmitted.

 

 

SETTINGS