Hardware setup

Connection via RJ45 wiring system

 

Master

 

 

 

 

1

Modbus cable depending on the type of master

 

 

 

 

 

 

 

1

 

 

 

 

 

2

Modbus splitter box

3

4

3

4

5

3

Modbus drop cables

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Modbus T-junction box

5

 

 

3

 

3

5

Line terminators

3

3

 

 

 

 

ATV 212

Description

RJ45 is factory set to connect the graphic display option.

Use the open style connector to connect the drive to Modbus fieldbus.

Using RJ45 to connect Modbus fieldbus is still possible but requires to modify parameter [Com channel choice] F807 value. Set F807 to 0 [RJ45].

RJ45 Reference

Connection accessories

Description

 

 

 

Reference

 

 

 

 

 

 

Modbus splitter block

 

10 RJ45 connectors and 1 screw terminal

LU9 GC3

 

 

 

 

 

Modbus T-junction boxes

With integrated cable (0.3 m)

VW3 A8 306

TF03

 

 

 

 

 

 

 

 

With integrated cable (1 m)

VW3 A8

306

TF10

 

 

 

 

 

 

Line

For RJ45 connector

R = 120

Ω, C = 1 nF

VW3 A8

306 RC

terminators

 

 

 

 

 

 

 

R = 150

Ω

VW3 A8

306 R

 

 

 

 

 

 

 

 

 

Connecting cables

Description

Length

Connectors

Reference

 

m

 

 

 

 

 

 

Cables for

3

1 RJ45 connector and 1 stripped end

VW3 A8 306 D30

Modbus bus

 

 

 

0.3

2 RJ45 connectors

VW3 A8 306 R03

 

 

 

 

 

 

1

2 RJ45 connectors

VW3 A8 306 R10

 

 

 

 

 

3

2 RJ45 connectors

VW3 A8 306 R30

 

 

 

 

RS 485 double

100

Supplied without connector

TSX CSA 100

shielded twisted pair

 

 

 

200

Supplied without connector

TSX CSA 200

cables

 

 

 

 

500

Supplied without connector

TSX CSA 500

 

 

 

 

Type of master

Master interface

Modbus connection accessories for RJ45 wiring system

 

 

 

 

 

 

 

 

 

Description

Reference

 

 

 

 

 

Twido PLC

Adaptor or mini-DIN RS485

3 m cable fitted with a mini-DIN connector and an RJ45

TWD XCA RJ030

 

interface module

connector

 

 

 

 

 

 

 

 

Adaptor or screw terminal

3 m cable fitted with an RJ45 connector and stripped at the other

VW3 A8 306 D30

 

RS485 interface module

end

 

 

 

 

 

 

 

TSX Premium PLC

TSX SCY 11601 or

Cable fitted with a SUB-D 25 connector and stripped at the other

TSX SCY CM 6030

 

TSX SCY 21601 module

end (for connection to the screw terminals of the LU9GC3 splitter

 

 

 

(SUB-D 25 socket)

block)

 

 

 

 

 

 

 

 

PCMCIA card (TSX SCP114)

Stripped cable

TSX SCP CM 4030

 

 

 

 

 

 

 

 

 

 

14

S1A53844 01/2011

Page 14
Image 14
Schneider Electric Altivar 212 Connection via RJ45 wiring system, RJ45 Reference, Description, Connection accessories