Parameter list

Examples:

Run forward (CMOd and FMOd configured to serial communication)

FA00 = 16# 0400

Run reverse (CMOd and FMOd configured to serial communication)

FA00 = 16# 0600

Run forward, commands and setpoint from Modbus (irrespective of CMOd and FMOd)

FA00 = 16# C400

Run reverse, commands and setpoint from Modbus (irrespective of CMOd and FMOd)

FA00 = 16# C600

Command word 2 (FA20)

Bit

Function

0

1

Note

 

 

 

 

 

0

Reserved

-

-

-

 

 

 

 

 

1

Energy reset

No reset

Reset

Input energy (FE76)

 

 

 

 

Output energy (FE77)

 

 

 

 

 

2 to 11

Reserved

-

-

Do not set to "1"

 

 

 

 

 

12

Over-current stall level change

OC stall 1

OC stall 2

OC1 (F601), OC2 (F185)

 

 

 

 

 

13 to 15

Reserved

-

-

Do not set to "1"

 

 

 

 

 

Energy reset (bit 1):

This command is enabled regardless of the command priority selection (bit 15 of common word (FA00)). It is necessary to reset it after the command is performed.

Over-current stall level change (bit 12):

This command word is enabled only when the communication command is enabled. Set Bit 15 of the Command word (FA00) to "1" [enabled].

This command word will be disabled is set (value 0), power is turned off or is reset, or factory setting [Parameter reset] (tYP) is selected.

S1A53844 01/2011

49

Page 49
Image 49
Schneider Electric Altivar 212 manual Examples, Command word 2 FA20, Energy reset bit, Over-current stall level change bit