Parameter list
Status
Status word (FE0I Fd01)
Status immediately before the occurrence of a trip: [Communication Number] (FE01)
Current status: [Communication Number] (Fd01)
Bit | Specifications | 0 | 1 | Remarks |
|
|
|
|
|
0 | FL state | Not active | Active |
|
|
|
|
|
|
1 | Drive state | Not tripped | Tripped | Trip statuses include rtry |
|
|
|
| and trip retention status. |
|
|
|
|
|
2 | Alarm | No alarm | Alarm issued |
|
|
|
|
|
|
3 | MOFF | Normal | MOFF | Main circuit undervoltage |
|
|
|
| alarm. |
|
|
|
|
|
4 | Motor section (1 or 2) | Motor 1 (THR 1) | Motor 2 (THR 2) | THR1: PT=set value, uL, ub, |
| (THR 2 selection) |
|
| Thr |
|
|
|
| THR2: PT=0, F170, F172, |
|
|
|
| F173 |
|
|
|
|
|
5 | PI control OFF | PI control permitted | PI control prohibited |
|
|
|
|
|
|
6 | Acceleration/deceleration | Acceleration/deceleration | Acceleration/deceleration | AD1: ACC, DEC, |
| pattern selection (1 or 2) | pattern 1 (AD 1) | pattern 2 (AD 2) | AD2: F500, F501 |
|
|
|
|
|
7 | DC braking | OFF | Forced DC braking |
|
|
|
|
|
|
8 | Reserved | - | - |
|
|
|
|
|
|
9 | Forward/reverse run | Forward run | Reverse run |
|
|
|
|
|
|
10 | Run/stop | Stop | Run |
|
|
|
|
|
|
11 | Coast stop (ST=OFF) | ST=ON | ST=OFF |
|
|
|
|
|
|
12 | Emergency stop | Not emergency stop | Emergency stop status |
|
|
| status |
|
|
|
|
|
|
|
13 | Standby ST=ON | Standby | Standby: Initialization | |
|
|
|
| completed, not detected fault |
|
|
|
| stop status, not alarm stop |
|
|
|
| status (MOFF, LL forced stop |
|
|
|
| or forced stop due to a |
|
|
|
| momentary power OFF), |
|
|
|
| ST=ON, and RUN=ON |
|
|
|
|
|
14 | Standby | Standby | Standby: Initialization | |
|
|
|
| completed, not detected fault |
|
|
|
| stop status, and not alarm stop |
|
|
|
| status (MOFF, LL forced stop |
|
|
|
| or forced stop due to a |
|
|
|
| momentary power OFF) |
|
|
|
|
|
15 | Local/Remote status | Remote | Local | Command is "FA08" |
|
|
|
|
|
S1A53844 01/2011 | 51 |