Configuration

Control by the Modbus network or the terminals, switched via Modbus

The commands come from the terminals if bit 15 of the command word [Command from serial communication] (FA00) is "OFF" (value 0).

The commands come from the Modbus network if bit 15 of the command word (FA00) is "enabled" (value 1).

The setpoint comes from the terminals if bit 14 of the command word (FA00) is "OFF" (value 0).

The setpoint comes from the Modbus network if bit 14 of the command word (FA00) is "enabled" (value 1).

The LOC/REM key is valid.

Below is the list of parameters that must be configured.

Access to the parameters

Parameters

Location

 

 

[Command mode sel] (CMOd)

[PROGRAMMING MENU] Programming mode

[Frequency mode sel] (FMOd)

 

 

 

[Com channel choice] (F807)

[COMMUNICATION MENU] COM submenu of

 

[PROGRAMMING MENU] Programming mode.

 

 

Description

Parameters

 

 

 

 

 

 

 

Modbus

 

Setting

 

 

 

Default

 

Valid

 

 

 

 

 

 

 

 

 

 

address

 

 

 

 

 

 

 

setting

 

after

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Command mode sel] (CMOd)

 

 

3

 

0 [Logic inputs]

 

0

 

 

Setting

Remote mode start/stop control

 

 

16#3

 

Control terminal logic inputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Frequency mode sel] (FMOd)

 

 

4

 

1 [Ref source VIA]

 

1

 

 

Setting

Remote mode primary speed reference source

 

16#4

 

The source of the drive’s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

speed reference is VIA.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Com channel choice] (F807)

 

 

2055

 

0 [RJ45] or

 

1

 

 

Setting

Selection of Communication channel: via RJ45 or

 

16#807

 

1 [Open style]

 

 

 

 

 

 

 

 

Open style connector port

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 15 of

 

 

 

 

 

 

 

 

 

Terminals

 

 

 

 

 

 

 

 

command word FA00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Serial com. command

 

 

 

LOC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Commands CMOd

 

 

 

 

 

 

 

priority bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REM

 

Modbus commands

ON

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminals

 

 

 

 

 

 

 

 

 

 

REM

Commands

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation panel

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Modbus

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOC

 

 

 

 

 

commands

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

 

 

 

 

 

 

Setpoint FMOd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VIA

 

Modbus setpoint

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VIB

 

2

 

 

 

 

 

 

 

 

REM

 

Setpoint

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation panel

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Bit 14 of

 

 

 

 

 

 

 

 

Modbus setpoint

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOC

 

 

 

 

 

 

 

 

 

 

 

command word FA00

 

 

 

 

 

 

 

UP/DOWN

 

5

 

 

 

Communication

Operation

 

 

 

 

 

 

 

 

 

 

Serial com. setpoint

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F807

 

 

 

 

 

 

priority bit

panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RJ45 channel: Modbus

Network channel: Paremeter F829

0

1