Modbus services

Write multiple registers (16)

Function 16 = 16#10, quantity =1

This function code is used to write a block of contiguous registers (1 to approx. 120 registers). Read only parameters can't be written.

Request:

Slave no.

Function

Starting

Quantity of register

Byte count

First register value

-------

 

code

address

 

 

 

 

 

 

 

10

 

 

00

01

02 (fixed)

 

 

 

 

 

 

(fixed)

(fixed)

 

 

 

 

 

 

 

 

 

 

 

1 byte

1 byte

2 bytes

2 bytes

1 byte

2 bytes

CRC16

2 bytes

Response:

Slave no.

Function code

Starting address

Quantity of register

CRC16

 

10

 

 

00 (fixed)

01 (fixed)

 

 

1 byte

1 byte

2 bytes

2 bytes

2 bytes

Error response:

Slave no.

Function code

Exception code

CRC16

 

 

 

90

 

 

 

1 byte

1 byte

1 byte

2 bytes

Refer to "Error response", page 41.

Example: Write value 60Hz in the parameter [Frequency reference from serial comm.] (FA01) in Altivar 212 slave 1.

Request:

01

10

FA 01

00 01

02

17 70

F3 9A

Response:

01

10

FA 01

00 01

60 D1