Configuration

Configuration of the indirect blocks

Configuration

These parameters configure the Modbus functions "Read indirect block (3)", page 34 and "Write indirect block (16)", page 38.

Access to the parameters

All parameters are accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode.

Description

Parameters

Modbus

Adjustment range

Default

Valid

 

address

 

 

setting

after

 

 

 

 

 

 

[Block write data 1] (F870)

2160

0

[No select]: No selection

 

 

 

16#870

1

[Command word 1]

 

 

 

 

2

[Command word 2]

0

Power

 

 

3

[Frequency Setpoint]

 

 

cycle

[Block write data 2] (F871)

2161

4

[Relay command]: Ouput data on the terminal board

 

 

16#871

5

[FM command]: Analog output for communication

 

 

 

 

6

[Speed Setpoint]

 

 

 

 

 

 

 

 

[Block read data 1] (F875)

2165

0

[No select]: No selection

 

 

 

16#875

 

 

 

1

[Status info]

 

 

[Block read data 2] (F876)

2166

2

[Freq. out]: Output frequency

 

 

 

16#876

3

[Motor current]: Ouput current

 

 

 

 

4

[Ouput volt]: Ouput voltage

 

Power

[Block read data 3] (F877)

2167

 

5

[Alarm info]: Alarm information

0

 

16#877

6

[PID feedback value]

cycle

 

 

 

 

7

[Input term. mon]: Input terminal board monitor

 

 

[Block read data 4] (F878)

2168

 

 

8

[Out term. mon]: Output terminal board monitor

 

 

 

16#878

 

 

 

9

[VIA monitor]: VIA terminal board monitor

 

 

 

 

10 [VIB monitor]: VIB terminal board monitor

 

 

[Block read data 5] (F879)

2169

 

 

11 [Mot speed mon.]: Ouput motor speed monitor

 

 

 

16#879

 

 

 

 

 

 

 

 