Configuration

Control by the terminals, monitoring by the Modbus network

The commands and the setpoint come from the terminals.

The Altivar 212 is monitored via the Modbus network.

The LOC/REM key is valid.

Below is the list of parameters that must be configured.

Access to the parameters

Parameters

Location

 

 

[Command mode sel] (CMOd)

[PROGRAMMING MENU] Programming mode

[Frequency mode sel] (FMOd)

 

 

 

[Com channel choice] (F807)

[COMMUNICATION MENU] COM submenu of

 

[PROGRAMMING MENU] Programming mode.

 

 

Description

 

Parameters

 

 

 

 

 

Modbus

 

Setting

 

 

Default

Valid

 

 

 

 

 

 

 

 

address

 

 

 

 

 

 

 

setting

after

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Command mode sel] (CMOd)

 

3

 

0 [Logic inputs]

 

 

0

Setting

 

Remote mode start/stop control

 

16#3

 

Control terminal logic inputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Frequency mode sel] (FMOd)

 

4

 

1 [Ref source VIA]

1

Setting

 

Remote mode primary speed reference source

16#4

 

The source of the drive’s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

speed reference is VIA.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Com channel choice] (F807)

 

2055

 

0 [RJ45] or

 

 

1

Setting

 

Communication channel selection

 

16#807

 

1 [Open style]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 15 of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

command word FA00

 

LOC

 

 

Commands CMOd

 

Serial com. command priority bit

 

 

 

Modbus commands

ON

 

 

 

REM

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

Terminals

 

 

 

 

 

 

 

 

REM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Commands

Operation panel

 

1

 

 

 

 

 

 

 

 

 

Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Modbus

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

commands

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setpoint FMOd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

VIA

 

 

 

 

 

Modbus setpoint

ON

 

 

VIB

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation panel

 

3

 

 

 

 

 

 

 

 

 

Operation

 

 

 

 

 

 

 

 

OFF

Modbus

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setpoint

 

 

Communication

 

 

Bit 14 of

panel

 

 

 

 

UP/DOWN

 

5

 

 

 

 

 

 

command word FA00

 

 

 

 

 

 

 

 

F807

 

 

 

 

 

 

 

 

Serial com. setpoint priority bit

 

 

 

 

 

 

 

 

 

 

 

 

 

RJ45 channel: Modbus

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Network channel:

 

1

 

 

 

 

 

 

 

 

 

 

Paremeter F829

 

 

 

 

 

 

 

REM

LOC

Setpoint

22

S1A53844 01/2011

Page 22
Image 22
Schneider Electric Altivar 212 manual Control by the terminals, monitoring by the Modbus network, Parameters