Parameter list

Referring to the Altivar 212 programming manual

General

Parameters are decribed in the Altivar 212 programming manual.

For communication purposes, the section "Table of parameter and data" references Modbus address, unit, range... The table below is an abstract, just for example.

Additionnal parameter, not listed in the Altivar 212 programming manual, are described in the present section.

Submenu or parameter

Modbus

Setting

Unit

Default

description

address

 

 

setting

 

 

 

 

 

[5 LAST PARAM CHANGE] (AUH)

 

Operation panels parameters in groups of five in

-

-

History function

 

the reverse order to that in which their settings

 

 

 

 

were changed (possible to edit).

 

 

 

 

 

 

 

[Quick menu] (AUF)

 

The AUF submenu provides ready access to

-

-

Wizard function

 

the ten basic parameters commonly used in

 

 

 

 

programming the drive.

 

 

 

 

In many cases, programming the ATV212 drive

 

 

 

 

is complete when these 10 parameters and

 

 

 

 

motor parameters have been properly set.

 

 

 

 

 

 

 

[Auto ramp] (AUI)

0

0 [Disabled]: Manual

-

1

Automatic acceleration/ deceleration

16#0

1 [Enable]: [Acceleration time 1] (ACC) and

 

 

 

 

[Deceleration time 1] (dEC)

 

 

 

 

2 [ACC only]: [Acceleration time 1] (ACC) only

 

 

 

 

 

 

 

[Acceleration time 1] (ACC)

9

0.0 to 3200

s

According

Slope of the acceleration ramp and

16#9

 

 

to drive

the time it takes for the output

 

 

 

model

frequency of the

 

 

 

 

drive to increase from 0 Hz to the

 

 

 

 

setting of [Max frequency] (FH)

 

 

 

 

 

 

 

 

 

"Modbus address" identifies the parameter for communication.

In Modbus protocol, it is also called "register address" or "Parameter address".

"Adjusment range" or "Range" means the data cannot be written outside the range.

The data is expressed in the decimal notation. For writing the data through the communication function, take the minimum setting unit into consideration, and use hexadecimal notation.

"Minimum setting unit" is the unit of a single data.

For example, the "Minimum setting unit" of [Acceleration time 1] (ACC) is 0.1. 1 corresponds to 0.1s. For setting the ACC to 10 seconds, transmit 16#03E8 by communication [10÷0.01=1000=16#03E8].

44