Configuration

Command by the Modbus network, setpoint by the Modbus network or the terminals switched to by a logic input

The commands come from the Modbus network.

The setpoint comes from the Modbus network if logic input R is OFF.

The setpoint comes from the terminals if logic input R is ON.

The function 38 [Frequency source] is assigned to the logic input R, F112 = 38.

The LOC/REM key is valid.

Below is the list of parameters that must be configured.

Access to the parameters

Parameters

Location

 

 

 

 

 

 

 

 

 

 

[Command mode sel] (CMOd)

[PROGRAMMING MENU] Programming mode

 

 

 

[Frequency mode sel] (FMOd)

 

 

 

 

 

 

 

 

 

 

 

[Com channel choice] (F112)

[I/O MENU] IO submenu of [PROGRAMMING MENU]

 

 

Programming mode.

 

 

 

 

 

 

 

 

[Remote spd ref 2] (F207)

[EXTENDED MENU] F---submenu of [PROGRAMMING

 

MENU] Programming mode.

 

 

 

 

 

 

 

 

 

[Com channel choice] (F807)

[COMMUNICATION MENU] COM submenu

 

 

 

 

of [PROGRAMMING MENU] Programming mode.

 

 

 

 

 

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

Parameters

Modbus

Setting

Default

 

Valid

 

address

 

setting

 

after

 

 

 

 

 

 

[Command mode sel] (CMOd)

3

2 [Communication]

0

 

Setting

Remote mode start/stop control

16#3

Serial communication

 

 

 

 

 

 

 

 

 

[Frequency mode sel] (FMOd)

4

4 [Serial com ref.]

1

 

Setting

Remote mode primary speed reference source

16#4

Serial communication

 

 

 

 

 

 

 

 

 

[LI R selection] (F112)

274

38 [Frequency source]

6

 

Setting

R logic input function

16#112

Configured to Frequency reference

 

 

 

 

 

source switching

 

 

 

 

 

 

 

 

 

[Remote spd ref 2] (F207)

519

1 [VIA]: VIA

2

 

Setting

Remote mode secondary speed reference source

16#207

 

 

 

 

that may override the source selected by FMOd

 

 

 

 

 

 

 

 

 

 

 

[Com channel choice] (F807)

2055

0 [RJ45] or

1

 

Setting

Selection of Communication channel: via RJ45 or

16#807

1 [Open style]

 

 

 

Open style connector port

 

 

 

 

 

 

 

 

 

 

 