Modbus services

Write Single Register (6)

The Write Single Register function permits to write value of one parameter. Not all Altivar 212 parameters can be written.

Request and response:

Slave no.

Function code

Register address

Register value

CRC16

 

06

Hi

 

Lo

Hi

 

Lo

Lo

 

Hi

 

 

 

 

1 byte

1 byte

 

2 bytes

 

2 bytes

2 bytes

Error response:

Slave no.

86

Exception code

CRC16

Lo

Hi

 

 

 

 

 

1 byte

1 byte

1 byte

1 byte

Example: Write value 60 Hz to the parameter [Frequency reference from serial comm.] (FA01) in Altivar 212 slave 1.

Request and response:

01

06

FA01

1770

E6C6

Example: Error response due to invalid register address.

Request:

01

06

FFFF

0000

89EE

Error response:

01

86

02

C3A1

36