Hardware setup

Ethernet bridge

Screw terminal RS485

3 m cable fitted with an RJ45 connector and stripped at the other

VW3 A8 306 D30

(TSX ETG 100)

 

end

 

 

 

 

 

Serial port PC

Male SUB-D 9 RS232 serial

RS232/RS485 converter and

TSX SCA 72 and

 

port PC

3 m cable fitted with an RJ45 connector and stripped at the other

VW3 A8 306 D30

 

 

end (for connection to the screw terminals of the LU9GC3 splitter

 

 

 

block)

 

 

 

 

 

Protection Against Interference

Use the Schneider Electric cable with 2 pairs of shielded twisted conductors (reference: TSXCSA100, TSXCSA200, TSXCSA500).

Keep the Modbus cable separated from the power cables (30 cm (11.8 in.) minimum).

Make any crossovers of the Modbus cable and the power cables at right-angles, if necessary.

For more information, please refer to the TSX DG KBL E manual: “Electromagnetic compatibility of industrial networks and fieldbuses”.

S1A53844 01/2011

15

Page 15
Image 15
Schneider Electric Altivar 212 manual Protection Against Interference