Modbus services

Read indirect block (3)

Function 3, quantity = 1 ... 5

The Read indirect block function permits to read 1 to 5 parameters. These parameters can be chosen by parameters F875 ... F879 (refer to "Configuration of the indirect blocks", page 27)

Access to the parameter

This parameter is accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode.

Description

Parameters

Modbus

Adjustment range

Default

Valid

 

address

 

 

setting

after

 

 

 

 

 

 

[Block read data 1] (F875)

2165

0

[No select]: No selection

 

 

 

16#875

1

[Status info]

 

 

 

 

2

[Freq. out]: Output frequency

 

 

[Block read data 2] (F876)

2166

 

 

3

[Motor current]: Ouput current

 

 

 

16#876

 

 

 

4

[Ouput volt]: Ouput voltage

 

Power

[Block read data 3] (F877)

2167

5

[Alarm info]: Alarm information

0

 

16#877

6

[PID feedback value]

cycle

 

 

 

 

7

[Input term. mon]: Input terminal board monitor

 

 

[Block read data 4] (F878)

2168

 

 

8

[Out term. mon]: Output terminal board monitor

 

 

 

16#878

 

 

 

9

[VIA monitor]: VIA terminal board monitor

 

 

[Block read data 5] (F879)

2169

10 [VIB monitor]: VIB terminal board monitor

 

 

 

16#879

11 [Mot speed mon.]: Ouput motor speed monitor

 

 

 

 

 

 

 

 

Request:

Slave no.

Function code

Starting address

Quantity of registers

CRC16

 

03

Hi

Lo

Hi

 

Lo

Lo

Hi

 

18 (fixed)

75 (fixed)

00

 

02 to 05

 

 

 

 

 

 

 

1 byte

1 byte

2 bytes

 

2 bytes

2 bytes

Response:

Slave no.

Function code

Byte count

First register value

 

03

 

Hi

 

Lo

 

 

 

 

 

 

1 byte

1 byte

1 byte

 

2 bytes

-------

Last register value

CRC16

Hi

 

Lo

Lo

Hi

 

 

 

 

 

 

2 bytes

2 bytes

Error response:

Slave no.

Function code

Exception code

CRC16

 

83

 

Lo

Hi

1 byte

1 byte

1 byte

1 byte

Example: Read indirect block in an drive with slave address 1.

Configuration parameters:

[Block read data 1] (F875) = 1: [drive Status] (Fd01)

[Block read data 2] (F876) = 2: [Output frequency] (Fd00)

[Block read data 3] (F877) = 3: [Output current] (FE03)

[Block read data 4] (F878) = 4: [Output voltage] (FE05)

[Block read data 5] (F879) = 5: [Alarm code] (FC91)

Read indirect block of 5 parameters:

Request:

01

03

18 75

00 05

92 B3

Response:

01

03

0A

64 04

17 70

00 00

26 FB

00 80

1E 29

34