Parameter list

Monitoring and control of I/O from communication

The digital inputs, digital outputs, analog input and output signals of the drives can be controlled by communication.

Digital inputs status (Fd06, FE06)

Digital inputs status immediately before the occurrence of a trip: [Status of input terminal block] (FE06)

Current digital inputs status: [Status of input terminal block] (Fd06)

In case "0: No assignment function" is selected in function selection, drive operations will not be affected even when terminals are turned

on and off. Therefore, the terminals can be used as input terminals for customer's own use.

The input terminal function selection parameter is used to select a function for each input terminal.

Bit

Terminal name

Function (parameter title)

0

1

 

 

 

 

 

0

F

[LI F selection] (F111)

OFF

ON

 

 

 

 

 

1

R

[LI R selection] (F112)

OFF

ON

 

 

 

 

 

2

RES

[LI RES selection] (F113)

OFF

ON

 

 

 

 

 

3 to 6

Reserved

-

-

-

 

 

 

 

 

7

VIA (1)

[VIA LI selection] (F118)

OFF

ON

 

 

 

 

 

8 to 15

Reserved

-

 

 

 

 

 

 

 

(1): It is valid only when it is selected as contact input by [VIA Input Function] (F109).

Example: When both F and RES terminals are ON: FE06 = 16#0005

FE06:

BIT 15

 

 

 

 

 

 

 

 

 

BIT 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

0

0

0

0

0

0

0

0

0

0

0

0

1

0

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

0

 

 

 

0

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital outputs status (Fd07, FE07)

Digital outputs status immediately before the occurrence of a trip: [Status of output terminal block] (FE07)

Current digital outputs status current status: [Status of output terminal block] (Fd07)

The output terminal function selection parameter is used to select a function for each output terminal.

Bit

Terminal name (extended)

 

Function (parameter title)

0

1

 

 

 

 

 

 

0

RY

 

Output terminal selection1 (F130)

OFF

ON

 

 

 

 

 

 

1

Reserved

 

-

-

-

 

 

 

 

 

 

2

FL

 

Output terminal selection3 (F132)

OFF

ON

 

 

 

 

 

 

3 to 15

Reserved

 

-

-

-

 

 

 

 

 

Example: When both the RY and FL terminals are ON: FE07 = 16#0005

 

 

 

BIT 15

BIT 0

 

 

FE07:

0

0

0

0

0

0

0

0

0

0

0

0

0

1

0

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

0

 

 

 

0

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S1A53844 01/2011

55

Page 55
Image 55
Schneider Electric Altivar 212 manual Monitoring and control of I/O from communication, Digital inputs status Fd06, FE06