Analog Comparators

LD Language Elements

Analog Comparators

Description

The Analog Comparators function block is used to:

 

z Compare a measured analog value with an internal reference value.

 

z Compare two measured analog values.

 

z Compare two measured analog values with hysteresis parameter.

 

The result of this comparison is used in the form of a contact.

 

Analog automation functions can be used for smart relays with a real time clock and

 

DC power supply, and with mixed DISCR/Analog inputs.

 

The following indicate the existence of mixed Discrete/Analog inputs:

 

z The existence of inputs numbered from IB to IG (maximum configuration). These

 

 

inputs are used to receive analog signals from 0.0 V to 9.9 V inclusively.

 

z The presence of the Analog Comparators function in the toolbar of the

 

 

programming software.

 

These smart relays have 16 Analog Comparators function blocks, numbered from

 

1 to 9 then from A to G.

Use as a Contact

 

 

 

The contact shows the position of a measured analog value in relation to a reference

 

value or to another measured value.

 

It may be used as many times as necessary in the program. It may be used

 

according to 2 modes: normally open or normally closed, described below.

 

Normally open mode:

 

Symbol of the normally open contact associated with a, Analog Comparator:

 

 

 

 

 

 

A-

 

 

 

 

 

 

The contact is conducting when the comparison condition is verified.

 

Normally closed mode:

 

Symbol of the normally closed contact associated with an analog comparator:

 

 

 

 

 

a-

 

 

 

 

 

 

The contact is conducting when the condition is not verified.

 

 

 

 