relay:

LD Language Elements

Configuration from Front Panel

Configuration screen of a Clock function block from the front panel of the smart

relay:

1

2

3

 

 

 

7

H 1 D / W

0 _ 2 _ _ 5 6

 

C

 

 

 

 

H : M O N

0 1 : 1 0

4

6

H : M O F F

2 3 : 5 9

5

 

-

+

 

 

 

 

 

Menu / OK

 

Number Parameter

Description

1Clock module number 8 clocks available, numbered 1 to 8.

2Type of date configuration D/W: Days of the Week,

3

Validity day (D/W type)

Validity day:

z0: Monday,

z1: Tuesday,

z...

z6: Sunday.

Unselected days are indicated by a _.

4Start time (D/W type) This is the operation start time, in Hour: Minute format (00.00 to 23:59).

5Stop time (D/W type) This is the operation end time, in Hour : Minute format (00.00 to 23:59).

6

Parameter lock

Locking prevents locked parameters from being

 

 

 

 

 

 

modified from the front panel of the smart relay

 

 

 

 

 

 

 

 

 

 

 

 

using the PARAMETERS menu.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

Operating ranges

4 operating ranges are available: A, B, C, D.

 

 

 

 

 

 

In operation, these ranges are cumulative: The

 

 

 

 

 

 

block is valid over all selected ranges.

If the clock is set to ON on Monday at 23:00 and set to OFF on Monday at 1:00, then it does not change to OFF on Tuesday at 1:00 but effectively on the following Monday at 1:00. Moreover, if no other command has been made, the clock remains positioned at ON all other days of the week.